Megger RCDT330 Residual Current Device Tester
- Manufacturer Certificate Included
- Auto RCD Test
- Ramp Test
- Polarity Selection
- Data Storage
- Auto RCD
- Data storage
- Non-Trip RCD
- Polarity Test
- Ramp Test
-
-
Information on the calibration of newly purchased equipment and what it means to you.
Calibration and its certification comes in varying forms on new equipment and in this section, we will break it down into the three areas that we use to classify calibration state at the point of purchase.
Manufacturers Calibration Certificate
This is a calibration certificate offered by the manufacturer supplied with the tester. This is also known as an end-of-line certificate or manufacturer’s certificate. These certificates vary depending on the manufacturer and product. They will not have your company's name on them and don’t always show proven test results.
Where applicable we will include the following statement relating to the item/s on the products page under the heading *Important Calibration Information.
This instrument comes complete with the manufacturer's calibration certificate. Please be aware that these certificates are generic and may also be time-lapsed.
If you would prefer a personalised full traceable calibration certificate applied to the equipment before dispatch, then please select this option from the drop-down menu above, an additional calibration charge will apply.Manufacturers Certificate of Conformity
A manufacturer's certificate of conformity is not a calibration certificate. It is merely a statement that the equipment has been produced to operate within its intended application, it has no traceable certificate or constitutes any defined results for accuracy before leaving the manufacturing process.
Where applicable we will include the following statement relating to the item/s on the products page under the heading *Important Calibration Information.
This instrument comes with a ‘manufacturer's certificate of conformity’. It is important to understand that this does NOT constitute a ‘calibration certificate’. A certificate of conformity merely states that the equipment has been designed and produced to meet the requirements of its intended application.
Where calibration of an instrument is possible we will offer this as a separately purchasable item and may be selected from the drop-down box above. You will be sent a full traceable calibration certificate produced in our laboratory and applied with your details as required.Personalised traceable calibration certificate from isswww
This is a calibration certificate created by us at ISS. This certificate is fully traceable to national and international standards. The certificate will show your company's details, tester information, proven test results and the equipment used to carry out the test. Nearly 90% of all calibrations we do are done in-house in one of our many fully equipped laboratories. You can add this service to your order on the product page before you checkout.
Where applicable we will include the following statement relating to the item/s on the products page under the heading *Important Calibration Information.
We are on occasion able to offer FREE calibration on certain products at their point of sale (newly purchased equipment only) please look out for the following badge on the product's page to take advantage of this free offer.
-
-
Megger RCDT300 Series Residual Current Device Tester
The RCDT330 additionally offers the facility to save test results to internal memory. Over 1000 result can be saved on site, and downloaded to a computer when convenient. Data is stored in non-volatile memory, being retained when the instrument is switched off or batteries are exhausted. A Job reference number can be selected for a range of results, allowing separate locations to be tested with the same tester and easily separated when downloaded. A memory bar graph acts as a ‘Fuel Gauge’ showing how much memory has been used Test results are downloaded to CSV (Comma Separated Variable) spreadsheets, and can be imported into Microsoft Excel®. If certificates or reports are required, the results can be downloaded directly into Megger Powersuite Professional with a range of features for creating professionally finished documentation for NICEIC, ECA BS and other standard formats.
Key Features:
- n Tests standard, DC, selective, and programmable RCDs
- Ramp testing n Auto (Remote) testing
- 3 Phase safe n Enables testing on 110 V centre tapped supplies.
- Tough rubber armoured case with built-in cover
- Weatherproof to IP54
- USB interface for downloading test result
Description:
Standard test ranges
- The RCDT300 series can perform 1/2I, 1xI and 5xI tests on RCDs rated at 30 mA, 100 mA, 300 mA and 500 mA on general and selective (time delayed) RCDs. The RCDT320/ 330 can also test RCDs rated at 10 mA and 1000 mA. All units offer DC testing of RCD’s.
Test times for normal and Selective RCDs are:
Normal Selective
1/2I 2s 2s
I 300ms 2s
5I 40ms 150ms
- 5I tests are available on RCDs rated up to 100 mA.
Polarity
- All RCD's can be tested at 0° or 180°
- Selective breakers have a time delay in tripping. When selected, trip test times are extended and a 30s delay is allowed between the measurement of the fault voltage and the application of the test current.
- Touch Voltage is measured at the start of the RCD test. If enabled it is displayed on the analogue arc on completion of testing.
- Designed to take the bashing that testers receive on site, the Megger RCDT testers are rubber armoured.
- The rigid display cover folds right out of the way during testing and locks down to protect the display when it is finished.
- No buried functions mean it is obvious how to use the Megger RCDT.
- Colour coded ranges help test range selection, reducing test times and fault location.
- A user guide in the lid provides all the basic information. Hands free use
- It hangs comfortably around the neck for hands-free use because the instrument is carefully balanced.
- DC sensitive RCDs can be tested at 1/2I, 1xI and 5xI.
- (RCDT320/330) n To measure the trip current of an RCD. Current level is slowly increased from 1/2I to 1I (+10%). When the RCD trips the trip current is displayed and held on the screen.
- Very useful diagnosing nuisance tripping of RCDs.
Megger RCD300 Series Selection Guide
Key Features | Manufacturer Certificate Included, Auto RCD Test, Ramp Test, Polarity Selection, Data Storage | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Product Stock Status | Next Day Delivery (subject to availability) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Manufacturer | Megger | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short Description |
Updated January 2024
Please note, our cut-off time is 2:00pmOrders requiring calibrationWhilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery. Bank/Public HolidaysPredicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scopeof our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order. *UK Mainland (Revised March 2021)
Delivery SurchargesBecause of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:
Offshore ServicesAll offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles. International deliveryInternational delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk ExportAll export inquiries should be directed to the export division before placement of order. If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.