Megger MPCC230 Pro Circuit Checker 1015-876
-
-
Information on the calibration of newly purchased equipment and what it means to you.
Calibration and its certification comes in varying forms on new equipment and in this section, we will break it down into the three areas that we use to classify calibration state at the point of purchase.
Manufacturers Calibration Certificate
This is a calibration certificate offered by the manufacturer supplied with the tester. This is also known as an end-of-line certificate or manufacturer’s certificate. These certificates vary depending on the manufacturer and product. They will not have your company's name on them and don’t always show proven test results.
Where applicable we will include the following statement relating to the item/s on the products page under the heading *Important Calibration Information.
This instrument comes complete with the manufacturer's calibration certificate. Please be aware that these certificates are generic and may also be time-lapsed.
If you would prefer a personalised full traceable calibration certificate applied to the equipment before dispatch, then please select this option from the drop-down menu above, an additional calibration charge will apply.Manufacturers Certificate of Conformity
A manufacturer's certificate of conformity is not a calibration certificate. It is merely a statement that the equipment has been produced to operate within its intended application, it has no traceable certificate or constitutes any defined results for accuracy before leaving the manufacturing process.
Where applicable we will include the following statement relating to the item/s on the products page under the heading *Important Calibration Information.
This instrument comes with a ‘manufacturer's certificate of conformity’. It is important to understand that this does NOT constitute a ‘calibration certificate’. A certificate of conformity merely states that the equipment has been designed and produced to meet the requirements of its intended application.
Where calibration of an instrument is possible we will offer this as a separately purchasable item and may be selected from the drop-down box above. You will be sent a full traceable calibration certificate produced in our laboratory and applied with your details as required.Personalised traceable calibration certificate from isswww
This is a calibration certificate created by us at ISS. This certificate is fully traceable to national and international standards. The certificate will show your company's details, tester information, proven test results and the equipment used to carry out the test. Nearly 90% of all calibrations we do are done in-house in one of our many fully equipped laboratories. You can add this service to your order on the product page before you checkout.
Where applicable we will include the following statement relating to the item/s on the products page under the heading *Important Calibration Information.
We are on occasion able to offer FREE calibration on certain products at their point of sale (newly purchased equipment only) please look out for the following badge on the product's page to take advantage of this free offer.
-
-
Megger MPCC230 Pro Circuit Checker 1015-876
The Megger MPCC230 is a compact socket tester and circuit checker, in one unit.
It is designed to allow the user to test the correct wiring polarity of a socket as well as check the circuit earth loop and protective RCD during routine maintenance or inspection. In addition, the condition of the mains voltage supply can be measured, along with frequency, and an indication of the total harmonic distortion displayed. The advanced features make the MPC230 an invaluable circuit checker. Incorrect polarity is shown in detail
and - because of the TFT colour display - indicated clearly by a red test bar. With the ability to measure earth loop impedance on RCD protected circuits, as well as calculate the prospective earth fault current and show the touch voltage value, it aids routine inspection of an installation.
An auto-RCD test will confirm the operation of the protective device at measure the contact voltage value. In addition, the MPCC230 will not only provide the TRMS supply voltage, but also indicate the total harmonic distortion measured and allow the user to identity which harmonics are present.
With a memory function capable of storing up to 64 loop impedance or RCD test values, these can be downloaded using the free app for simple report generation.
Features:
- TRMS professional socket checker
- 30 mA Type A, AC and F RCD Test
- AUTO RCD x1/2, x1, x5 and 180°
- Touch voltage indication
- Frequency measurement
- Earth loop impedance with prospective earth fault current
- THD% of mains voltage
- Voltage harmonics indication, up to the 49th
Advanced Features:
- Socket polarity
- TRMS Voltage measurement
- AUTO RCD test (Type A, AC and F)
- RCD contact voltage
- No-trip earth loop impedance test with low and extra- low test current modes and touch voltage indication
- Prospective earth fault current display
- Voltage harmonics up to the 49th
- THD% (Total harmonics distortion)
- Results storage for up to 64 loop and RCD tests
- Dedicated results app - Megger Pro Circuit Checker
- Adaptor App
The MCPP230 will execute the following tests:
1. Socket polarity
2. TRMS voltage and frequency
3. Protective device (RCD/RCBO) type A, AC and F
4. No-trip earth loop impedance
5. Prospective earth fault current and touch voltage
6. Voltage harmonics up to 49th
7. THD% (Total harmonics distortion)
Tests are selected by pressing the FUNC button.
Sub-function features can be selected through the F1 and F2 buttons, for example for selecting the RCD type or displaying different harmonics.
The instrument is powered through the line input, but with the supercap technology, the display will remain visible. Fully charged, the supercap will allow ~45 seconds of use after switch off from the line. This allows the user to remove the unit and read the displayed result. This is useful, should the socket be mounted in a hard to access location.
4.1 Volt and socket test
This feature measures Voltage between phase and neutral and tests the socket wiring and polarity in accordance to local requirement.
4.1.1 Operation
1. Plug the instruments into the socket and press the FUNC button to select the Voltage function.
2. Voltage between Phase and Neutral will be shown on the display. Pressing the F2 button will cycle to the measured frequency and the units firmware and serial number. Pressing F1 cycles back to voltage.
2.1. If the socket wiring is correct and the measured earth touch voltage is less than 50 V, a green bar indicates all parameters are correct.
2.2. If an error occurs due to incorrect wiring or a high voltage detected on the earth, the bar will
turn red and an audible alarm will sound. The unit will display the failed parameter on the screen (examples in Fig 2 and 3).
RCD Auto-Operation
4.2.2 RCD x1/2, x1, x5 and Auto Operation
1. Plug the instruments into the socket and press the FUNC button to select the RCD function.
2. Press the F1 button to select the type of RCD and F2 button to select the current (x1/2, x1, x5 or Auto).
3. Press and hold the RED test button for 3 seconds to start the test.
4. The trip time and contact voltage results are shown on the display.
4.1. A green bar indicates the trip time and contact voltage are within specification (Fig 4).
4.2. If the trip time exceeds the predefined pass levels (refer to table in Auto RCD section below) or the contact voltage >50 V, a red bar is shown, indicating a fail.
4.2.3 RCD AUTO function
1. Plug the instrument in the socket and press FUNC button to select the RCD function.
2. Press the F1 button to select the type of RCD and F2 button to select AUTO.
3. Press the RED test button to start the test.
4. The instruments will execute all tests in sequence, reset the RCD between each step.
■ AUTO mode consist of 6 test in the following sequence:
Loop Test
CAUTION : The MPCC230 uses a low current no-trip loop test method. However, this DOES NOT guarantee an RCD will not trip. Accumulative or highly sensitive RCDs or RCBOs may still trip, so care should be taken to ensure that a loss of supply will not cause a hazardous situation to arise.
4.3.1 Test modes:
■ V Measures Impedance Zs (Z L-Pe) (Ω) and Touch Voltage (V) (Fig.8)
■ I Measures Impedance Zs (Z L-Pe) (Ω) and IPEFC Prospective Earth Fault Current (Fig.9)
■ Std Test with 15 mA nominal current
■ Low Test with 6 mA. Use this setup if during the test the RCD trip due to the presence of leakage current in the electric system under test.
4.3.2 LOOP test operation
1. Plug the instruments into the socket and press the FUNC button to select the LOOP function.
2. Press the F1 button to select V or I and F2 button to select TEST STD or LOW.
3. Press and hold the RED test button for 3 seconds to start the test.
fig 8 fig 9
WARNING : During the LOOP measurement, if the SUPERCAP is not fully charged, the display may switch off or decrease the intensity, however the measurement will be performed and shown at the end.
4.4 HAR voltage harmonics
This function checks the quality of the line voltage with regards to harmonics.
4.4.1 Test mode:
■ Fund Indicates the fundamental on the bar graph and displays the measured voltage and frequency. Total harmonic distorion (THD) is diaplayd as a percentage (Fig. 10).
■ h2....h50 Shows the selected harmonic on the bar graph in red, along with the measured voltage and frequency. A harmonic distortion %, compared to the fundamental, is also displayed
Harmonics function
1. Plug the instruments into the socket and press the FUNC button to select “HAR” function.
2. Press the F1 and F2 buttons to select harmonics value required
It is possible to disconnect the instrument from the power supply to read and analyse the measurements, until the SUPERCAP is discharged (approx 45 second when fully charged).
fig 10 fig 11
4.5 MEM Memory / REPORT
The instrument automatically saves RCD and LOOP measurement to the internal memory.
It is possible to store 64 consecutive measurement results. The results will be organized in chronological order with the last measurement saved in the first cell.
4.5.1 Operation
1. Plug the instruments into the socket and press the FUNC button to select MEM
2. Press F1/F2 buttons to move through the saved data
3. Press both F1 and F2 to enter clear memory mode
4. Press FUNC to clear memory or F2 to cancel
4.5.2 Report create
5. In MEM mode, press the RED button to generate a results QR code on the display (Fig.12)
6. With the Megger Pro Circuit Checker App running on your mobile device, select “Scan QR”. All saved measurements will be imported to the App and displayed in a simple report. This can then be exported in either PDF or csv format. All saved measurements will be included in a REPORT with the possibility of exporting in pdf or csv.
7. Download the Megger Pro Circuit Checker App for iOS and Android devices on the Google Play or
Apple App store.
Memory Function
8. Fig. 13 shown the MEM results display. Column No is the internal memory cell number. FUNC shows the test type and Value indicates the measured result.
9. For saved RCD measurements, a pass or fail value is shown as either GREEN or RED:
9.1. GREEN if the result has passed the test.
9.2. RED if the result has not passed the test.
isswww and Megger
The extensive Megger product portfolio provides electrical test equipment for an exceptionally wide range of applications at any point of the electricity network. From small handheld low voltage equipment such as multifunction installation testers through to high voltage asset test equipment like insulation resistance testers, circuit breaker analysers, protection relay test systems to transformer condition measurement devices.
Megger designs and manufactures portable electrical test equipment in factories located in Germany, Sweden, the UK, and USA. Megger products help you install, improve efficiency, reduce cost and extend the life of you or your customers’ electrical assets.
Established in the late 1800s, the company has been designing and making test and measurement instruments that perform electrical measurements for preventative maintenance, troubleshooting and commissioning for decades. Megger products have supported customers all over the world to improve their facilities’ efficiency, reduce costs, extend the life of apparatus and through trending and analysis, anticipate equipment failure and future performance. Being a brand synonymous with the industry and a cornerstone pioneer of many of today’s everyday items of test equipment, ISSWWW are proud to bring you Megger’s full range of equipment and services, now and into the future.
Product Stock Status | Next Day Delivery (subject to availability) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Megger | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short Description |
|
Updated January 2024
Please note, our cut-off time is 2:00pm
Orders requiring calibration
Whilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery.
Bank/Public Holidays
Predicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scopeof our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order.
*UK Mainland (Revised March 2021)
Service | Price |
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value OVER £75.00 ex VAT | FREE |
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value UNDER £75.00 ex VAT | £4.95 |
Next WORKING Day (excludes Saturdays, Sundays and public holidays) – UK Mainland only - Zones A & B - ANY order value - Order by 2:00pm | £7.75 |
Saturday ANYTIME Delivery - Order by 2:00pm | £9.95 |
Delivery Surcharges
Because of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:
- Zones A & B - Mainland delivery rates apply.
- Zone C - Scottish Highlands (Charges are calculated at the checkout).
- Zone D - Outer Hebrides, Orkney Isles, Shetland Isles, Isle of Man, Scilly Isles, and Channel Islands (Charges are calculated at the checkout).
- Zone E - Northern Ireland (Charges are calculated at the checkout).
- Zone F - Republic of Ireland (Charges are calculated at the checkout).
Offshore Services
All offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles.
International delivery
International delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk
Export
All export inquiries should be directed to the export division before placement of order.
If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
All stated prices are subject to VAT at the current rate where applicable.
E&OA