The images provided are for illustrative purposes only. Please refer to product description.

Fluke 1662 Multifunction Installation Tester

The New Fluke 1660 Series. The Fluke 1662 is a solid, basic installation tester.

Next Day Delivery (subject to availability)

£660.00 including VAT @ 20% £550.00 excluding VAT Regular Price: £996.00
  • Phase Rotation Service
  • Auto RCD
  • Backlit LCD Display
  • Non Trip Loop Testing
  • FreeDelivery
  • 30DayMoneyBack
Required Fields
  • Description
  • Features/Specs
  • Resources
  • Delivery

 

Free Gift For Multifunction Testers

The New Fluke 1662

Solid, Entry Level Multifunction Tester

The 1662 puts more power in your hands by quickly and efficiently testing to all local regulations, protecting appliances that may be inadvertently connected to the system under test, and making it easy to share test results over your smartphone. Safety and performance are two of the most critical requirements for any electrical system. Good quality insulation, a properly working grounding system and active protection assure the safety of people, electrical systems and buildings, and protect them against electrocution, fire and other equipment damage.

Fluke 1662 Multifunction Installation Tester Includes:

  • 6x AA (IEC LR6) cell batteries
  • C1600 hard carrying case
  • Zero adapter
  • Heavy duty mains cord
  • STD standard test lead set
  • C1600 hard carrying case
  • Padded carrying and waist strap
  • Quick reference guide
  • TP165X remote control probe and lead
  • User's manual on CD-ROM

The versatility of the Fluke Multifunction Tester

Insulation-continuity test: our installation tester does the job.
Fluke installation testers can be used to perform an insulation-continuity test, which is designed to diagnose and prevent the breakdown of the insulation in various parts of the electrical system such as wires, transformers and motors. The quality of insulation is critical to assure proper, uninterrupted and safe functioning of electrical circuits.

Checking RCD devices with a Fluke multifunction tester.
Our versatile installation testers can also check the proper functioning of residual-current devices (RCDs). RCDs are designed to disconnect quickly to mitigate the harm caused from electric shock and to avoid current leaks that may lead to fire and other dangerous situations. Our installation testers assure that RCDs can properly perform this important task.

The perfect loop testing tool: a Fluke installation tester.
Loop testing is a quick, convenient, and highly specific method of evaluating an electrical circuit for its ability to engage protective devices (circuit breakers, fuses, RCDs). A ground loop determines the effectiveness of protective devices.

Resistance measurement of grounding systems.
The electrical installation testing abilities of the Fluke installation tester also include verification tests to ensure that a system's resistance is low enough to provide protection to people, equipment and structures. A properly functioning grounding system is a critical safety feature of an electrical system.

 Measurement functions:

  • Measurement function
  • Voltage & frequency
  • Wiring polarity checker, detects broken N wires
  • Insulation resistance
  • Continuity & resistance
  • Measure motor windings with continuity test
  • Loop & line resistance
  • Prospective earth fault current (PEFC/IK)
  • Prospective short-circuit current (PSC/IK)
  • RCD switching time
  • RCD tripping level (ramp test)
  • Measures trip time & current for RCD type A & AC in one test
  • RCD variable current
  • Automatic RCD test sequence
  • Phase sequence indicator

Other features:

  • On/Off switchable auto-start for RCD & Looptest
  • Self-test
  • Illuminated display
  • Time and date (when used with optional FlukeView software)

 

Fluke 1660 Series Comparison Guide

What’s new. What’s different. Which is the right model?

The new Fluke 1660 Series Multifunction Installation Testers are the only installation testers that help prevent damage to connected appliances, while allowing users to wirelessly e-mail results from the field. Auto Test does all required installation tests in one sequence, ensuring compliance with local installation regulations.

Old Model

New Model

Features Changes – What’s New

1651

1662

  • RCD tripping current level ramp test
  • RCD auto test and ramp test
  • Pulsating dc sensitive RCD tests (G & S-type)
  • Remote probe
  • On/Off switchable auto-start for RCD and Looptest
  • Heavy duty, single input line cord
  • Computer interface

1652

1662

  • On/Off switchable auto-start for RCD and Looptest
  • Heavy duty, single input line cord
  • Computer interface

1653

1663

  • Continuity at L-N, N-PE inputs
  • On/Off switchable auto-start for RCD and looptest
  • Z max memory
  • Heavy duty, single input line cord

1654

1664 FC

  • Insulation-PreTest™ safety function
  • Insulation at L-N, N-PE inputs
  • Automatic test sequence
  • Continuity at L-N, N-PE inputs
  • Fluke Connect® compatibility
  • ShareLive™ Calling
  • FlukeCloud™ Storage
  • On/Off switchable auto-start for RCD and looptest
  • Z max memory
  • Heavy duty, single input line cord

Measurement Function

1664 FC

1663

1662

Insulation-PreTest™ safety function New

*

 

 

Insulation at L-N, N-PE and L-PE inputs New

*

 

 

Automatic test sequence New

*

 

 

Loop and line resistance–mΩ resolution

*

 

 

Continuity at L-N, N-PE and L-PE inputs New

*

*

 

Test smooth dc sensitive RCDs (Type B)

*

*

 

Earth resistance

*

*

 

Voltage (True-rms) and frequency

*

*

*

Wiring polarity checker, detects broken PE and N wires

*

*

*

Insulation resistance Continuity and resistance

*

*

*

Measure motor windings with continuity test (@ 10 mA)

*

*

*

Loop and line resistance

*

*

*

Prospective earth fault current (PEFC/IK)

*

*

*

Prospective short-circuit current (PSC/IK

*

*

*

RCD switching time 

*

*

*

RCD trip time 

*

*

*

RCD trip current (ramp test)

*

*

*

 Measures trip time and current for RCD type A & ac in one test

*

*

*

RCD variable test current

*

*

*

Automatic RCD test sequence

*

*

*

Phase sequence test  

*

*

*

Other features

 

 

 

Fluke Connect Compatibility New     

*

 

 

ShareLive™ Calling New 

*

 

 

FlukeCloud™ Storage New

*

 

 

On/Off switchable auto-start for RCD and loop test New

*

*

*

Self-test 

*

*

*

Illuminated display       

*

*

*

Memory, interface

 

 

 

Z max memory New 

*

*

 

Memory

*

*

 

IR-USB and BLE interface (use with optional Fluke DMS and FVF software)

IR-USB/BLE

IR-USB

 

Included accessories

 

 

 

Heavy duty, single input line cord New

*

*

*

Hard case

*

*

*

Remote control probe

*

*

*

Zero adapter

*

*

*

AC voltage measurement
Range 500 V
Resolution 0.1 V
Accuracy 45 Hz – 66 Hz 0.8% + 3
Input impedance 360 kΩ
Overload protection 660 V rms
Continuity testing (RLO)
Range (autoranging) 20 Ω / 200 Ω / 2000 Ω
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage >4 V
Insulation resistance measurement (RISO)
Test voltages 100-250-500-1000 V
Accuracy of tTest voltage (at rated test current) +10%, -0%
Test voltage 50 V
100 V
250 V
500 V
1000 V
Insulation resistance range 20 MΩ /50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ
Resolution 0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current 1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ
Loop and line impedance (ZI)
Range 10 Ω / 0.001 Ω / High current mΩ mode
Resolution 0.01 Ω / 0.1 Ω / 1 Ω
Prospective earth fault current, PSC test
Range 1000 A / 10 kA (50 kA)
Resolution 1 A / 0.1 kA
Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type AC¹
G²,S³
Model 1662 A4, AC¹, G²,S³
Notes ¹Responds to AC 
²General, no delay
³Time delay
4Responds to pulsed signal
5Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹ 10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplier x ½, x 1
x 5
Measurement range RCD Type G 310 ms
50 ms
RCD Type S 510 ms
160 ms
Notes ¹1000 mA type AC only
700 mA maximum type A in VAR mode
VAR mode not available for type B.
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current range 30% to 110% of RCD rated current¹
Step size 10% of IΔN²
Dwell time Type G 300 ms/step
Type S 500 ms/step
Measurement accuracy ±5%
Specified trip current ranges (EN 61008-1) 50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
²5% for Type B
Notes ¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B
Phase Sequence Indication
Icon icon phase sequence indicator  Phase Sequence indicator is active.
General Specifications
Size (L x W x H) 10 x 25 x 12.5 cm
Weight (incl. batteries) 1.3 Kg
Battery size, quantity Type AA, 6 ea.
Sealing IP-40
Safety Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
Overvoltage CAT III / 500V; CAT IV 300V
Performance EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition

Standard Delivery 3-5 Day Delivery – UK
£2.95 for all all orders under £40.00 (exld vat). Sent by Royal Mail Tracked, delivered/posted within 3-5 working days from the date of your order, subject to availability.

Standard Free Delivery 3-5 Day Delivery – UK Mainland only - Zone A & B
Included in the price for all orders over £40.00 (exld vat). Sent using FedEx, delivered within 3-5 working days from the date of your order, subject to availability.

Express DPD Delivery 1-2 Day Delivery – UK Mainland only - Zone A & B
£4.50 select at the checkout. Sent using DPD on their Award Winning “Predict” Service with these great key benefits:

  • You are given a one hour delivery window. (no more waiting in all day for your parcel)
  • You are notified by text or e-mail on your parcels progress.
  • Change of plan? You can easily use the text or e-mail to rearrange your delivery.
  • Notifications on your parcel up to 15 minutes before delivery.

Orders must be placed before 3pm for next day delivery and a mobile number supplied, subject to availability.

Next Day Delivery – UK Mainland only - Zone A & B
£8.00 select at the checkout. Sent using FedEx, orders must be placed before 3pm for next day delivery, subject to availability.

Saturday Pre 12am - UK Mainland only - Zone A & B
£15.00 select at the checkout. Sent using FedEx, orders must be placed before 3pm for Saturday delivery.

Delivery Surcharges
Because of the high cost of carriage we need to apply a surcharge on all deliveries made in the following regions: 

  • Scotland, Isle of Wight & Isles of Scilly - £6.00  
  • Scottish Highlands and Northern Ireland - £12.00  Zone C
  • Scottish Islands, Isle of Man and Channel Islands - £14.00  Zone D
  • Southern Island - £15.00  Zone E

 

 International delivery

International delivery charges are automatically added to your order at the checkout; you can also use the guide below for a guide on prices. For any questions regarding international deliveries please contact us at sales@isswww.co.uk

 Zone 1:

  • France, Germany, Belgium, Netherlands, Luxembourg. £20.00 per parcel

Zone 2:

  • Austria, Denmark. £22.00 per parcel
  • Liechtenstein, Switzerland £47.00 per parcel (added cost for custom clearance surcharge)

Zone 3:

  • Czech Republic, Italy, Slovakia, Spain. £28.00 per parcel

Zone 4:

  • Estonia, Finland, Hungary, Poland, Portugal, Slovenia, Sweden. £50.00 per parcel

Zone 5:

  • Bulgaria, Croatia, Greece (incl islands) Latvia, Lithuania, Romania. £60.00 per parcel

Bosnia-Herzegovina, Iceland, Norway, Serbia. £85.00 per (added cost for custom clearance surcharge)

If no shipping option is available to your selected country.  Please call us on +44 (0) 1603 406 148 to purchase your items.