The MTR105 is a dedicated rotating machine tester that brings Megger’s proven insulation resistance (IR) expertise together with advanced low resistance, capacitance, inductance, and rotation testing in one handheld instrument. It delivers a holistic view of motor health, enabling you to assess windings, connections, and overall condition with precision and confidence. Designed for production, service, and maintenance teams, the MTR105 supports fast, reliable decisions across your asset lifecycle.

Comprehensive testing capabilities

Built on a unified test architecture, the MTR105 consolidates multiple core measurements:

  • Insulation resistance with PI, DAR, timed tests, and temperature compensation for consistent, comparable results.
  • DLRO four‑wire Kelvin low resistance testing for accurate measurement of joints, connections, and windings.
  • Inductance and capacitance to characterise coils and diagnose imbalance or deterioration.
  • Motor direction of rotation and three‑phase supply rotation to verify correct installation before energisation.

This integrated approach reduces set‑up time, cuts the number of tools you carry, and streamlines workflows in the field or workshop.

Accuracy you can trust

Stable test voltages and four‑wire measurement techniques underpin consistent, repeatable readings. Temperature measurement and compensation keep IR results aligned to reference conditions, so trends are meaningful across seasons and sites. Clear, full‑colour graphics present values and trends at a glance, allowing you to validate pass/fail criteria and move decisively to the next task.

Safety engineered into every test

The MTR105 is designed to protect both operator and instrument. Fast live‑voltage detection inhibits tests if hazardous voltage is present, reducing the risk of damage when connected to energised circuits or across phases. User‑selectable test terminal lockout thresholds add another layer of control, while robust internal protection supports safe use in CAT III 600 V environments.

Robust by design, ready for the field

A tough, over‑moulded housing and IP54 environmental protection defend against dust, moisture, and daily knocks. Detachable, interchangeable leads adapt to different applications and maintain reliable connections. With onboard storage for up to 256 motors and simple USB download, you can capture, share, and analyse results as part of a connected maintenance ecosystem.

Confident, efficient decision‑making

By unifying essential motor tests in a single instrument, the MTR105 helps you shorten diagnostics, standardise procedures, and improve asset reliability. Whether you are commissioning new equipment, verifying repairs, or conducting routine maintenance, the MTR105 provides the clarity, safety, and durability you need to work with confidence.

Technical Specifications 

Specifications - All quoted accuracies are at 20ºC (68ºF)
Insulation resistance
Volts Accuracy
50 V 10 GΩ ±2% ±2 digits ±4.0% per GΩ
100 V 20 GΩ ±2% ±2 digits ±2.0% per GΩ
250 V 50 GΩ ±2% ±2 digits ±0.8% per GΩ
500 V 100 GΩ ±2% ±2 digits ±0.4% per GΩ
1000 V 200 GΩ ±2% ±2 digits ±0.2% per GΩ
Polarisation index (PI) 10 min / 1 minute ratio
Dielectric absorption ratio (DAR) User configurable 15 s or 30 s t1
start time with t2 fixed at 60 s
Guard terminal performance
<5% error at 500 kΩ parallel circuit resistance with 100 MΩ load
Resolution 0.1 kΩ
Short circuit/charge current
2 mA +0% -50% (IEC61557-2)
Terminal voltage accuracy -0% +2% ±2 V
Test current
1 mA at min. pass value of insulation to a max. of 2 mA
Operation range 0.10 MΩ to 1.0 GΩ (IEC61557-2)
Leakage current display 0.1 uA resolution 10% (±3 digits)
Voltage display ±3% ±2 digits ±0.5% of rated voltage
Note Above specifications only apply when high-quality silicone leads are being used - as supplied with the instrument.
Continuity 
Measurement 0.01 Ω to 1 MΩ (0 to 1000 kΩ analogue scale)
Accuracy ±3% ±2 digits (0 to 99.9 Ω
±5% ±2 digits (100 Ω - 500 kΩ)
Test current 200 mA (–0 mA +20 mA) (0.01 Ω - 4 Ω)
Polarity Single or Dual (factory default) polarity
Lead resistance Null up to 10 Ω
Selectable current limit 20 mA and 200 mA
Capacitance 
Range 0.1 nF - 1 mF
Accuracy ±5.0% ±2 digits (1 nF - 10 μF)
Voltmeter 
Range dc: 0 - 1000 V
ac: 10 mV - 1000 V
TRMS sinusoidal (15 Hz - 400 Hz)
Accuracy dc: ± 2% ±2 digits (0 - 1000 V)
ac: ± 2% ±2 digits
(10 mV - 1000 V TRMS)
Frequency range 15 - 400 Hz (50 mV - 1000 V)
Frequency resolution 0.1 Hz
Frequency accuracy ±0.5% ±1 digit
Diode Test Diode test accuracy: ±2% ±2 digits 0.01 V to 3.00 V
Display range 0.00 V to 3.00 V
Temperature Measurement and Compensation 
Thermocouple Type T (Type K and Type J)
Thermocouple range -20 °C to 200 °C (4 °F - 392 °F)
Instrument range -20 °C to 1000 °C (4 °F - 1832 °F)
Instrument resolution 0.1 °C (0.18 °F) 
Instrument accuracy ±1.0 °C ±20 digits (1.8 °F). (Basic accuracy stated assumes forward and reverse measurements.)
DLRO Four-Wire Kelvin Low Resistance 
Test current 200 mA dc
Range 1 mΩ to 10 Ω
Resolution 0.01 mΩ
Accuracy ± 0.25% rdg. ± 10 digits, accuracy stated includes forward and reverse measurements.
Inductance 
Range Accuracy Test Frequency
1 H ±(0.7 % +(Lx/10000) % +5 digits) 1 kHz
200 mH ±(1.0 % +(Lx/10000) % +5 digits) 120 Hz
±(0.7 % +(Lx/10000) % +5 digits) 1 kHz
20 mH ±(2.0 % +(Lx/10000) % +5 digits) 120 Hz
±(1.2 % +(Lx/10000) % +5 digits) 1 kHz
2 mH ±(2.0 % +(Lx/10000) % +5 digits) 1 kHz only
Results Srorage 
Storage capacity 256 motor results (date / time stamped)
Data download USB Type A (USB Mass Storage Device)
Power
Battery 6 x IEC LR6 1.5 V Alkaline (AA), IEC FR6 1.5 V Lithium (LiFeS2 ), IEC HR6 1.2 V NiMH (rechargeable option).
Battery life 10 motors per (complete suite of tests at 100 V into 100 MΩ) IEC61557-2 - test cycle, 1200 insulation tests with duty cycle of 5 s testing on 25 sec standby @ 500 V into 0.5 MΩ.
IEC61557-4 test cycle, 1200 continuity tests with duty cycle of 5 sec testing on 25 sec standby on 1 Ω resistance
Battery charging Mains battery charger kit.
Safety protection IEC61010-1 CAT III 600 V
EMC Industrial IEC61326
Temperature coefficient <0.1% per °C up to 1 GΩ
Environment 
Operating temperature range -10 °C to 50 °C (14 °F to 122 °F)
Storage temperature range -25 °C to 65 °C (-13 °F to 149 °F)
Humidity 90% RH at 40 °C (104 °F) max.
Calibration temperature 20 °C (68 °F)
Maximum altitude 3000 m (9843 ft.)
IP rating IP54
Physical
Display Full LCD colour screen with user-configurable backlight
Languages English, French, German and Spanish.
Dimensions 228 x 105 x 75 mm (8.98 x 4.1 x 2.95 in)
Weight 1.00 kg (2.2 lbs)
Fuse x2 500 mA (FF) 1000 V 32 x 6 mm ceramic fuse, high break capacity HBC, 30 kA minimum. Glass fuses must not be installed.
UK Mainland Order by 2pm for Next Day Delivery*
Under £25.00 £4.50
Over £25.00 FREE

UK Highlands & Islands Order by 2pm for Next Day Delivery*
Under £80.00 £15.00