TSI LCA501 Rotating Vane Anemometer KIT AFL72900002

£816.00 £680.00

TSI LCA301 & LCA501 Technical Specification

Velocity
Range 0.25 to 30 m/s (50 to 6,000 ft/min)
Accuracy ±1.0% of reading ±0.02 m/s (±4 ft/min)
Resolution 0.01 m/s (1 ft/min)
Duct Size
Range
LCA301 0.00399 - 90 m2  (0.043 - 900 ft2)
LCA501 0 - 46.45 m2    (0 - 500 ft2)
Volumetric Flow Rate
Range Actual range is a function of velocity and duct area
Resolution
LCA301 <100; 0.1 l/s, 0.1 m3/hr, 0.1 ft3/min
LCA501 <100; 0.01 l/s, 0.01 m3/hr, 0.01 ft3/min
Temperature
Range 5 to 45°C (40 to 113°F)
Accuracy ±1.0°C (±2.0°F) Resolution LCA301   0.1°C (1°F) Resolution LCA501   0.1°C (0.1°F)
Instrument Temperature Range
Operating 5 to 45°C (40 to 113°F)
Storage -20 to 60°C (-4 to 140°F)
Data Storage Capabilities (LCA501 only)
Range 12,700+ samples and 100 test IDs
Logging Interval (LCA501 Only)
Range From 1 second to 1 hour

Time Constant (LCA501 Only)

User Selectable
External Meter Dimensions
LCA301 1.2 cm x 28 cm x 6.5 cm (4.5 in. x 11 in. x 2.6 in.)
LCA501 8.4 cm x 17.8 cm x 4.4 cm (3.3 in. x 7 in. x 1.8 in.)
Meter Weight with Batteries
LCA301 329 g (11.6 oz.)
LCA501 270 g (9.6 oz.)
Power Requirements
LCA301 Four AA-size batteries or AC adapter
LCA501 9-volt battery
Specifications subject to change without notice.
TSI and the TSI Logo are registered trademarks, and Airflow, the Airflow logo and LogDat2 are trademarks of TSI Incorporated.

Description

TSI LCA501 Rotating Vane Anemometer KIT (Logging)

*Important Calibration Information:

This instrument comes complete with the manufacturer's calibration certificate. Please be aware that these certificates are generic and may also be time-lapsed.
If you would prefer a personalised full traceable calibration certificate applied to the equipment before dispatch, then please select this option from the drop-down menu above, an additional calibration charge will apply.

LCA501 KIT Comes Supplied With:

  • Instrument
  • TSI rectangular capture cone 
  • Carrying case 
  • Alkaline batteries 
  • Operation and service manual 
  • Calibration certificate
  • USB cable and downloading software 

Product Details:

The Airflow™ Instruments Rotating Vanes LCA501 is a hand-held digital Rotating Vane Anemometer used for air velocity and volumetric flow measurements. Ideal applications include supply and extract grilles and flow hood balancing, HVAC commissioning and troubleshooting, laboratory safety monitoring and air conditioning and ventilation duct checks. 

Key Features:

  • Calculates volumetric flow rate
  • Reversible 100 mm head allows readings at supply and extract grilles
  • Compatible with Aircone Flow Hoods
  • No density correction factors required
  • Automatic averaging of air velocity

Additional features LCA501

  • Measures velocity and temperature  
  • Sweep mode for one overall measurement  
  • Log, store, and recall data  
  • Download data to a PC  
  • Optional telescopic probe available  
  • Clear digital display 

Also Available:

Aircone Flow Hoods

Available here 

Aircone Flow Hoods are a fast and accurate method of maximizing the usefulness of your 100 mm rotating vane anemometers. For a modest investment, you can enhance the capability of your rotating vane, turning it into an air volume flow balancing tool.

Features and Benefits

  • Rectangular and circular cones available
  • Measures volumetric flow at grilles and diffusers in l/s, m3/h, or ft3/min
  • Reads air volume quickly and accurately
  • Excellent choice for small grilles
  • Meets the HM Government Building Regulations of 2010 when using the rectangular aircone

Specifications

Aircone Flow Hoods Size:
Rectangular cone 285 mm x 235 mm (11 in. x 9 in.)
Round cone 180 mm (7 in.) diameter
Range (with LCA301 or LCA501) 0 to 100 l/s, 0 to 360 m3/h (0 to 210 ft3/min)
Weight (includes case) 1.1 kg (2.4 lbs)

isswww and TSI Airflow

TSI Inc. serves a global market by investigating, identifying and solving measurement problems. As an industry leader in the design and production of precision measurement instruments, TSI partners with research institutions and customers around the world to set the standard for measurements relating to aerosol science, air flow, chemical analysis, indoor air quality, fluid dynamics, biohazard detection, and even scrap metal sorting and plastics identification. With headquarters based in the U.S. and field offices throughout Europe and Asia, TSI has established a worldwide presence in the markets we serve. Every day, our dedicated employees turn research into reality.
isswww have enjoyed a long and successful relationship with TSI Airflow, supplying a good number of their products every month to trade and industry sectors, where they continue to affirm themselves as a leading brand in their market.

Features & Specification

More Information
Key Features Cone included, LCD Display, Manufacturer Certificate Included, Calculates volumetric flow rate , No density correction factors required, Automatic averaging of air velocity, Measures velocity and temperature, Sweep mode for one overall measurement, Log/store and recall data, Download data to a PC, Optional telescopic probe available
Product Stock Status Next Day Delivery (subject to availability)
Manufacturer TSI Airflow
Short Description

TSI LCA301 & LCA501 Technical Specification

Velocity
Range 0.25 to 30 m/s (50 to 6,000 ft/min)
Accuracy ±1.0% of reading ±0.02 m/s (±4 ft/min)
Resolution 0.01 m/s (1 ft/min)
Duct Size
Range
LCA301 0.00399 - 90 m2  (0.043 - 900 ft2)
LCA501 0 - 46.45 m2    (0 - 500 ft2)
Volumetric Flow Rate
Range Actual range is a function of velocity and duct area
Resolution
LCA301 <100; 0.1 l/s, 0.1 m3/hr, 0.1 ft3/min
LCA501 <100; 0.01 l/s, 0.01 m3/hr, 0.01 ft3/min
Temperature
Range 5 to 45°C (40 to 113°F)
Accuracy ±1.0°C (±2.0°F) Resolution LCA301   0.1°C (1°F) Resolution LCA501   0.1°C (0.1°F)
Instrument Temperature Range
Operating 5 to 45°C (40 to 113°F)
Storage -20 to 60°C (-4 to 140°F)
Data Storage Capabilities (LCA501 only)
Range 12,700+ samples and 100 test IDs
Logging Interval (LCA501 Only)
Range From 1 second to 1 hour

Time Constant (LCA501 Only)

User Selectable
External Meter Dimensions
LCA301 1.2 cm x 28 cm x 6.5 cm (4.5 in. x 11 in. x 2.6 in.)
LCA501 8.4 cm x 17.8 cm x 4.4 cm (3.3 in. x 7 in. x 1.8 in.)
Meter Weight with Batteries
LCA301 329 g (11.6 oz.)
LCA501 270 g (9.6 oz.)
Power Requirements
LCA301 Four AA-size batteries or AC adapter
LCA501 9-volt battery
Specifications subject to change without notice.
TSI and the TSI Logo are registered trademarks, and Airflow, the Airflow logo and LogDat2 are trademarks of TSI Incorporated.

Delivery

Updated January 2024

Please note, our cut-off time is 2:00pm

Orders requiring calibration 

Whilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.
Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery.

Bank/Public Holidays

Predicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scope
of our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order.

*UK Mainland (Revised March 2021)

Service Price
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value OVER £75.00 ex VAT FREE
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value UNDER £75.00 ex VAT £4.95
Next WORKING Day (excludes Saturdays, Sundays and public holidays)  – UK Mainland only - Zones A & B  - ANY order value - Order by 2:00pm £7.75
Saturday ANYTIME Delivery - Order by 2:00pm £9.95
 

 

 

 

 

Delivery Surcharges

Because of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:

  • Zones A & B  - Mainland delivery rates apply. 
  • Zone C - Scottish Highlands (Charges are calculated at the checkout).
  • Zone D - Outer Hebrides, Orkney Isles, Shetland Isles, Isle of Man, Scilly Isles, and Channel Islands (Charges are calculated at the checkout).
  • Zone E - Northern Ireland (Charges are calculated at the checkout).
  • Zone F - Republic of Ireland (Charges are calculated at the checkout).

Offshore Services

All offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles.

International delivery

International delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk

Export 

All export inquiries should be directed to the export division before placement of order.

If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
All stated prices are subject to VAT at the current rate where applicable.
E&OA