Megger LTW325 2 Wire Non-trip Loop Impedance Tester maxZ R1+R2
Megger LTW325 Loop Tester | |
General Accuracy | |
All accuracy statements are based on: | |
Ambient Temperature | 23° ±2°C |
Nominal Voltage Source | 230V a.c ±1% |
Voltage Measurements | |
(ac only) | 50V to 440V |
Accuracy | ±2% ±1V |
Frequency Measurements | |
Range | 25Hz to 99.99Hz |
Accuracy | ±0.1Hz |
A warning will be shown if applied voltage exceeds 440V. Damage will occur if applied voltage exceeds 600V rms |
|
Loop Testing Accuracy | |
±5% ±0.03Ω | @230V a.c |
±10% ±0.03Ω | @100V a.c and 280V |
±10% ±0.03Ω | @100V a.c and 300V a.c |
±15% ±0.03Ω | @50V a.c |
No Trip Loop and High Current Loop Test | |
Source Voltage | 50V to 440V (49Hz to 50.1Hz) |
Display Range | 0.01 to 2000Ω |
Accuracy | ±5% ± 0.03Ω |
No Trip Loop Test Nominal Current | 15ma (at nominal 230V a.c supply) |
High Current Loop Test | 4A (at nominal 230V a.c supply) |
Operational Range | 0.30 to 1000Ω |
Prospective Fault Current (PFC) | |
Prospective Fault Current | =Measured Source Voltage/Loop Resistance |
Maximum Range | No Trip Mode: 20KA |
Accuracy is derived from loop test and voltage measurement | |
Safety |
IEC 61010 |
EN61557 |
Complies with the following parts of EN61577: |
E.M.C | In accordance with IEC61326-1 |
Power Supply | |
Battery | 8 x 1.5V Cells IEC LR6 Type (AA Alkaline) |
Rechargeable | 8 x 1.2V NiCd or NIMH Cells |
Battery Life | 2000 consecutive tests |
Mechanical | |
Weight | 1000g ±10% excluding test leads |
Dimensions | 203 x 148 x 78mm |
Description
Megger LTW325 Earth Loop Tester
The entry-level tester in Megger's earth loop tester range, the LTW325 is used for carrying out 2 wire loop impedance measurements on phase to earth or phase to neutral.
Guaranteed not to trip working RCDs of more than 30mA thanks to a non-trip loop test and compatible with both three and single phase systems, this tester makes performing measurements easier by requiring the use of only 2 test leads in order to carry out measurement procedures. When there is no risk of tripping an RCD it is also possible to use high current loop testing mode.
When carrying out no-trip testing procedures the LTW325 constantly evaluates the level of noise detected on circuitry to ensure that the accuracy of results is not modified by the presence of electrical noise.
The Megger LTW325 is part of the LTW range of earth loop testers. The following table outlines the difference between each of the available models in this series.
Megger LTW325 Comes Supplied With:
- Megger LTW325 Earth Loop Tester
- BS1363 to 3 x 4mm Socket Leadset
- 2 Wire Leadset with Croc Clips
- Shuko Plug Test Lead – EU-SC
- AU/NZ Plug Test Lead – EU-AU
- Hard Carry Case
- User CD
Key Features:
- 2-wire loop testing procedures on phase to earth and phase to neutral
- Guaranteed to not trip out RCDs thanks to non-trip loop testing
- Noise detection filters out electrical noise that can create erratic readings
- Resolution down to 0.01Ω
- Portable lightweight instrument with tough carrying case encasing the tester
- AUTO start function starts testing as soon as the leads are connected
- PFC display up to 20kA
Megger LTW Series Selection Chart
Function | LTW315 | LTW325 | LTW335 | LTW425 |
2-Wire Non Tripping Loop Testing | X | X | X | X |
2-Wire Fast Test (High Current) | X | X | X | X |
110V to 280V Applications | X | X | X | X |
50V to 440V Applications | X | X | X | |
Phase to Phase Testing | X | X | X | |
20KA PFC Range | X | X | X | X |
40KA PFC Range | X | |||
0.01Ω Resolution | X | X | X | X |
0.001Ω Resolution | X | |||
AUTO Noise Detection | X | X | X | X |
AUTO Start Loop Test | X | X | X | X |
Voltage Measurements | X | X | X | X |
Frequency Measurements | X | X | X | X |
Max Zs Display | X | X | X | |
R2+R2 Display | X | X | X | |
Backlit Display (White Light) | X | X | X | X |
Built-In Front Cover (Foldaway) | X | X | X | X |
IP54 Weatherproof Case | X | X | X | X |
Accepts Rechargeable Batteries | X | X | X | X |
Test Result Storage | X | |||
Downloadable | X |
Features & Specification
Key Features | Manufacturer Certificate Included, 2 wire non-tripping loop test, 0.01 ohm resolution, PSC/PFC, Non Trip Testing | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Product Stock Status | Next Day Delivery (subject to availability) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Manufacturer | Megger | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short Description |
DeliveryUpdated January 2024
Please note, our cut-off time is 2:00pmOrders requiring calibrationWhilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery. Bank/Public HolidaysPredicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scopeof our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order. *UK Mainland (Revised March 2021)
Delivery SurchargesBecause of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:
Offshore ServicesAll offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles. International deliveryInternational delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk ExportAll export inquiries should be directed to the export division before placement of order. If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
|