Martindale ET4 Voltage Continuity Tester
DC Voltage
Range | Resolution | Input Impedance | Accuracy |
500mV | 0.1mV | 1.1MΩ | ± (0.5% of rdg + 2 dgts) |
5V | 0.001V | 1MΩ | |
50V | 0.01V | ||
500V | 0.1V | ||
600V | 1V |
Overload Protection: 600V DC or AC rms
AC Voltage
Range | Resolution | Input Impedance | Accuracy |
500mV | 0.1mV | 1MΩ |
Not specified |
5V | 0.001V | 50-60Hz ± (1.2% of rdg + 5 dgts) 60-500Hz ± (2.0% of rdg + 5 dgts) |
|
50V | 0.01V | ||
500V | 0.1V | ||
600V | 1V |
Overload Protection: 600V DC or AC rms
DC Current
Range | Resolution | Accuracy |
200A | 0.1A | ± (2.0% of rdg + 5 dgts) |
Maximum input current: 200A
AC Current
Range | Resolution | Accuracy (50 to 60Hz) |
200A | 0.1A | ± (2.0% of rdg + 5 dgts) |
Maximum input current: 200A
Frequency
Frequency measurement using AC current range
Range | Resolution | Accuracy |
30Hz to 400Hz | 0.1Hz | ± (0.1% of rdg + 5 dgts) |
Input sensitivity > 10A AC rms
Maximum input current: 200A AC rms
Resistance
Range | Resolution | Open Circuit Voltage | Accuracy |
500Ω | 0.1Ω | -3.2V DC | ± (1.0% of rdg + 5 dgts) |
5kΩ | 0.001kΩ | 1.1V DC Approx | |
50kΩ | 0.01kΩ | ||
500kΩ | 0.1kΩ | ||
5MΩ | 0.001MΩ | ± (1.5% of rdg + 5 dgts) | |
50MΩ | 0.1MΩ | ± (3.0% of rdg + 5 dgts) |
Overload Protection: 600V DC or AC rms
Continuity
Range | Resolution | Response Time | Accuracy |
500Ω | 0.1Ω | 100ms | <30Ω |
Overload protection: 600V DC or AC rms
Description
Martindale ET4 Voltage Continuity Tester
A compact electrical tester that measures voltage, resistance and current. It will also measure frequency, continuity and will take simultaneous measurement of current/voltage and frequency/voltage. This electrical tester can be used as a non-contact voltage indicator and has auto ranging, display hold and auto power off functions. One of the forks has a forward facing LED light to illuminate the area in the front.
The ET4 ComesSupplied With:
- Martindale ET4 Electrical Tester
- Martindale TL17 Test Leads
- 9V Battery
- Carry Case
- Instruction Manual
Key features:
- AC / DC Current: 0.1A to 200A
- AC / DC Voltage: 0.1mV to 600V
- Resistance: 0.1Ω to 50MΩ
- Frequency: 30Hz to 400Hz
- Continuity: 0.1Ω to 500Ω, buzz at <30Ω
- Diode Test: 1mV - 2V
- Non-Contact Voltage Indicator: 70V - 600V
- Power: 9V PP3 Alkaline (Included)
- Dimensions: 202 x 51 x 44mm
- Weight: 200g (incl. battery)
Features & Specification
Key Features | Non-contact voltage detector, LCD Display, Detachable Probes, Current Test, Tests Up To 600v | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Product Stock Status | Next Day Delivery (subject to availability) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Manufacturer | Martindale | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short Description | DC Voltage
Overload Protection: 600V DC or AC rms AC Voltage
Overload Protection: 600V DC or AC rms DC Current
Maximum input current: 200A AC Current
Maximum input current: 200A Frequency Frequency measurement using AC current range
Input sensitivity > 10A AC rms Maximum input current: 200A AC rms Resistance
Overload Protection: 600V DC or AC rms Continuity
Overload protection: 600V DC or AC rms DeliveryUpdated January 2024
Please note, our cut-off time is 2:00pmOrders requiring calibrationWhilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery. Bank/Public HolidaysPredicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scopeof our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order. *UK Mainland (Revised March 2021)
Delivery SurchargesBecause of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:
Offshore ServicesAll offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles. International deliveryInternational delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk ExportAll export inquiries should be directed to the export division before placement of order. If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
|