Fluke 1630-2 FC Earth Ground Clamp Meter | ||
Electrical Specifications | ||
Maximum voltage to earth ground | 1000 V | |
Battery type | AA alkaline IEC/EN LR6 (x4) | |
Battery life | More than 15 hours* | |
* In Ground Resistance measurement mode, with backlight turned off, and RF mode turned off | ||
Frequency range | 40 Hz to 1 kHz | |
Ingress protection | IEC/EN 60529: IP30 with jaw closed | |
LCD | Digital reading | 9999 counts |
Refresh rate | 4 per second | |
Operating temperature | -10 °C to + 50 °C | |
Storage temperature | -20 °C to + 60 °C | |
Operating humidity | Non condensing (<10 °C) (< 50 °F) | |
≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F]) | ||
≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F]) | ||
≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F]) | ||
(Non condensing) | ||
Operating altitude | 2000 m (6561 feet) | |
Storage altitude | 12 000 m (39,370 feet) | |
Reference temperature | 23 °C ±5 °C (73 °F ±9 °F) | |
Temperature coefficient | 0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F]) | |
Overload indication | OL | |
Data logging capacity | Minimum of 32,760 measurements | |
Data logging interval | 1 second to 59 minutes and 59 seconds | |
Display reading specification with standard loop resistance | ||
Input (Ω) | Minimum | Maximum |
0.474 | 0.417 | 0.531 |
0.5 | 0.443 | 0.558 |
10 | 9.55 | 10.45 |
100 | 96 | 104 |
Safety | ||
General | IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1 | |
Measurement | IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V | |
Current clamp for leakage current measurements | IEC/EN 61557-13: Class 2, ≤30 A/m | |
Resistance to earth | IEC/EN 61557-5 | |
Effectiveness of thepProtective measures | IEC/EN 61557-16 | |
Electromagnetic compatibility (EMC) | International | IEC/EN 61326-1: Portable Electromagnetic Environment |
CISPR 11: Group 1, Class B, IEC/EN 61326-2-2 | ||
Korea (KCC) | Class A equipment (Industrial Broadcast & Communications Equipment) | |
USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |
Wireless Radio | ||
Frequency range | 2412 MHz to 2462 MHz | |
Output power | <10 mW | |
Radio frequency certification | FCC ID:T68-FBLE IC:6627A-FBLE | |
General Specifications | ||
Conductor size | 40 mm (1.57 in) approximately | |
Dimensions (L x W x H) | 283 x 105 x 48 mm (11.1 x 4.1 x 1.9 in) | |
Weight | 880g (31 oz) | |
Warranty | One year | |
Earth Ground Loop Resistance | ||
Range | Accuracy1 ± (% of reading + Ω) | |
0.025 Ω to 0.249 Ω | 1.5% + 0.02 Ω | |
0.250 Ω to 0.999 Ω | 1.5% + 0.05 Ω | |
1.000 Ω to 9.999 Ω | 1.5% + 0.10 Ω | |
10.00 Ω to 49.99 Ω | 1.5% + 0.30 Ω | |
50.00 Ω to 99.99 Ω | 1.5% + 0.50 Ω | |
100.0 Ω to 199.9 Ω | 3.0% + 1.0 Ω | |
200.0 Ω to 399.9 Ω | 5.0% + 5.0 Ω | |
400 Ω to 599 Ω | 10.0% + 10 Ω | |
600 Ω to 1500 Ω | 20.00% | |
1 Loop resistance with no inductance, conductor centered and perpendicular to jaw | ||
Earth ground leakage current mA | ||
Autorange 50/60 Hz, True rms, crest factor CF ≤3 | ||
Range | Resolution | Accuracy1 ± (% of reading + mA) |
0.200 mA to 3.999 mA | 1 μA | 2.0% + 0.05 mA |
4.00 mA to 39.99 mA | 10 μA | 2.0% + 0.03 mA |
40.0 mA to 399.9 mA | 100 μA | 2.0% + 0.3 mA |
0.400 A to 3.999 A | 1 mA | 2.0% + 3 mA |
4.00 A to 39.99 A | 10 mA | 2.0% + 30 mA |
1 Applies to signal frequency
|
Description
Fluke 1630-2 FC Earth Ground Clamp Meter
Stakeless earth ground loop and ac leakage current clamp for fast, safe indoor/outdoor earth ground resistance
and ac leakage current tests.
Test the grounding components of equipment in hard-to-reach spaces, including areas that are indoors or fully paved and do not permit driving auxiliary test stakes. Stay on line—identify ground loop resistance without the need to disconnect then reconnect the earth electrode from the system. The Fluke 1630-2 FC Stakeless Earth Ground Clamp is the kind of high-quality, rugged tool you expect from Fluke. Heavy-duty clamp jaw stays in alignment and in calibration even in every day, on-the-job industrial environments.
Fluke 1630-2 FC Comes Supplied With:
- Earth Ground clamp
- Hard case
- Loop resistance standard
- 4 AA batteries
- Safety information guide
- Quick reference guide
Stakeless measurement
The 1630-2 FC clamp measures earth ground loop resistances for multi-grounded systems using the dual-clamp jaw. This test technique eliminates the dangerous and time-consuming activity of disconnecting parallel grounds, as well as the process of finding suitable locations for auxiliary test stakes. You can also perform ground tests in places that were previously difficult: inside buildings, on power pylons or anywhere you don’t have access to soil to place auxiliary test stakes.
Earth ground ac leakage current measurement
Identify ac leakage currents without disconnecting the earth ground stake from the grounding system–ideal for system troubleshooting.
Rugged
Heavy-duty clamp jaw stays in alignment and in calibration even in every day, on-the-job industrial environments.
Logging measurements
The earth ground clamp saves time by automatically recording data at pre-set intervals and saves up to 32,760 measurements in memory at the set logging interval. Saves time by recording and storing measured values.
Alarm threshold
User-defined high/low alarm limits, for rapid measurement evaluation.
Band-pass filter
Selectable band-pass filter function removes unwanted noise from the ac leakage current measurement.
Fluke Connect:
Fluke Connect® Wireless System
The 1630-2 FC supports the Fluke Connect Wireless System (may not be available in all regions). Fluke Connect wirelessly connects the clamp with an app on your smartphone or tablet. The app shows the ground resistance measurements on your smartphone or tablet display. You can save these measurements, GPS location from your phone and images to Fluke Connect Cloud storage and share with your team.
ISSWWW and Fluke Instruments
Fluke Corporation is the world leader in the manufacture, distribution and service of electronic test tools and software.
Since its founding in 1948, Fluke has helped define and grow a unique technology market, providing testing and troubleshooting capabilities that have grown to mission critical status in manufacturing and service industries. Every new manufacturing plant, office, hospital, or facility built today represents another potential customer for Fluke products.
From industrial electronic installation, maintenance and service, to precision measurement and quality control, Fluke tools help keep business and industry around the globe up and running. Typical customers and users include technicians, engineers, metrologists, medical-device manufacturers, and computer network professionals, people who stake their reputations on their tools, and use tools to help extend their personal power and abilities.
Fluke are a founding core supplier of ISSWWW and we enjoy a personal and professional relationship with them. Our sales staff and our technicians are Fluke trained and we hold perhaps the largest stock of their products in the country. Our customers know that when it comes to Fluke products, we have not only the best prices but the best advice and support services, reassuring when you need to make that all important purchase.
Features & Specification
Key Features | 40mm Jaw, Case Supplied, Includes Fluke Connect, Stakeless Testing, Ground Loop Resistance, Data Storage | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Fluke Testers | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short Description |
Product Stock Status |
Next Day Delivery (subject to availability) |
DeliveryUpdated January 2024
Please note, our cut-off time is 2:00pmOrders requiring calibrationWhilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery. Bank/Public HolidaysPredicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scopeof our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order. *UK Mainland (Revised March 2021)
Delivery SurchargesBecause of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:
Offshore ServicesAll offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles. International deliveryInternational delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk ExportAll export inquiries should be directed to the export division before placement of order. If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
|