Fluke 1587 FC Multimeter with Fluke Connect
Electrical Specifications | ||
AC voltage measurement | ||
Range | ||
600.0 mV | Resolution | 0.1 mV |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
6.000 V | Resolution | 0.001 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
60.00 V | Resolution | 0.01 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
600.0 V | Resolution | 0.1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3)¹ | |
1000 V | Resolution | 1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3)¹ | |
¹ 1 kHz bandwidth | ||
Low-Pass Filter Voltage | ||
Range | ||
600.0 mV | Resolution | 0.1 mV |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
6.000 V | Resolution | 0.001 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
60.00 V | Resolution | 0.01 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
600.0 V | Resolution | 0.1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
1000 V | Resolution | 1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
DC Voltage Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg + Counts) |
6.000 V dc | 0.001 V | ±(0.09% + 2) |
60.00 V dc | 0.01 V | ±(0.09% + 2) |
600.0 V dc | 0.1 V | ±(0.09% + 2) |
1000 V dc | 1 V | ±(0.09% + 2) |
Input impedance | 10 MΩ (nominal), <100 pF | |
Normal mode rejection ratio | >60 dB @ 50 Hz or 60 Hz | |
Common mode rejection ratio | >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalance) | |
Accuracies apply to ± 100% of range | ||
DC Millivolts Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg + Counts) |
600.0 mVdc | 0.1 mV | ±(0.1% + 1) |
DC and AC Current Measurement | ||
AC 45 Hz to 1000 Hz | ||
Range | 400 mA | |
Resolution | 0.1 mA | |
Accuracy ±(% of Rdg+Counts) | ±(1.5% + 2)¹ | |
Burden voltage (Typical) | 2 mV/mA | |
Range | 60 mA | |
Resolution | 0.01 mA | |
Accuracy ±(% of Rdg+Counts) | ±(1.5% + 2)¹ | |
Burden voltage (Typical) | 2 mV/mA | |
DC | ||
Range | 400 mA | |
Resolution | 0.1 mA | |
Accuracy ±(% of Rdg+Counts) | ±(0.2% + 2) | |
Burden voltage (Typical) | 2 mV/mA | |
Range | 60 mA | |
Resolution | 0.01 mA | |
Accuracy ±(% of Rdg+Counts) | ±(0.2% + 2) | |
Burden voltage (Typical) | 2 mV/mA | |
Overload | 600 mA for 2 minutes maximum | |
Fuse protection for mA input | 0.44 mA, 1000 V, IR 10 kA | |
AC conversion | Inputs are ac-coupled and calibrated to the rms value of sine wave input | |
Conversions are true-rms responding and specified from 5% to 100% of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor ≤1.5 at 600 mA. For non-sinusoidal waveforms add +(2% reading + 2% FS) typical, for a crest factor up to 3. | ||
¹ 1 kHz bandwidth | ||
Ohms Measurement | ||
Range | Resolution | Accuracy +(% of Rdg+Counts)¹ |
600.0 Ω | 0.1 Ω | ±(0.9% + 2) |
6.000 kΩ | 0.001 kΩ | ±(0.9% + 2) |
60.00 kΩ | 0.01 kΩ | ±(0.9% + 2) |
600.0 kΩ | 0.1 KΩ | ±(0.9% + 2) |
6.000 MΩ | 0.001 MΩ | ±(0.9% + 2) |
50.0 MΩ ² | 0.01 MΩ | ±(1.5% + 3) |
Overload protection | 1000 V rms or dc | |
Open circuit test voltage | <8.0 V dc | |
Short circuit current | <1.1 mA | |
¹ Accuracies apply from 0% to 100% of range ² Up to 80% relative humidity |
||
Diode Test | ||
Diode test indication | Display voltage drop: 0.6 V at1.0 mA nominal test current: | |
Accuracy | ±(2% + 3) | |
Continuity Test | ||
Continuity indication | Continuous audible tone for testresistance below 25 Ω and off above 100 Ω. Maximum Reading; 1000 Ω | |
Open circuit voltage | <8.0 V | |
Short circuit current | 1.0 mA typical | |
Overload protection | 1000 V rms | |
Response time | >1 m sec | |
Frequency Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts) |
99.99 Hz | 0.01 Hz | ±(0.1% + 1) |
999.9 Hz | 0.1 Hz | ±(0.1% + 1) |
9.999 kHz | 0.001 kHz | ±(0.1% + 1) |
99.99 kHz | 0.01 kHz | ±(0.1% + 1) |
Frequency Counter Sensitivity | ||
600.0 mV ac | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 100.0 mV |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 150.0 mV | |
DC Trigger Levels¹ to 20 kHz² | NA | |
6.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 1.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 1.5 V | |
DC Trigger Levels¹ to 20 kHz² | -400.0 mV and 2.5 V | |
60.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 10.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | 36.0 V | |
DC Trigger Levels¹ to 20 kHz² | 1.2 V and 4.0 V | |
600.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 100.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | - | |
DC Trigger Levels¹ to 20 kHz² | 12.0 V and 40.0 V | |
1000.0 V | V ac Sensitivity (RMS Sine Wave)¹ 5 Hz to 20 kHz | 300.0 V |
V ac Sensitivity (RMS Sine Wave)¹ 20 kHz to 100 kHz | - | |
DC Trigger Levels¹ to 20 kHz² | 12.0 V and 40.0 V | |
¹ Maximum input for specified accuracy = 10x range (1000 V max). Noise at low frequencies and amplitudes may affect accuracy ² Usable to 100 kHz with full scale input |
||
Capacitance | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts) |
1000 nF | 1 nF | ±(1.2% + 2) |
10.00 μF | 0.01 μF | ±(1.2% + 2) |
100.0 μF | 0.1 μF | ±(1.2% ±90 counts) |
9999 μF | 1 μF | ±(1.2% ±90 counts) |
Temperature Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts)¹ |
-40 ° C to 537 ° C | 0.1 °C | ±(1% + 10 counts) |
-40 ° F to 998 ° F | 0.1 °F | ±(1% + 18 counts) |
¹ Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument | ||
Insulation Specifications | ||
Measurement range | 0.01 MΩ to 2 GΩ | |
Test voltages | 50, 100, 250, 500, 1000 V | |
Test voltage accuracy | +20%, -0% | |
Short-circuit test current | 1 mA nominal | |
Auto discharge | Discharge time <0.5 second for C = 1 μF or less | |
Live circuit detection | Inhibit test if terminal voltage > 30 V prior to initialization of test | |
Maximum capacitive load | Operable with up to 1 μF load | |
Output Voltage | ||
50 V (0% to +20%) | Display range | 0.01 to 6.00 MΩ |
Resolution | 0.01 MΩ | |
Test current | 1 mA @ 50 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 6.0 to 50.0 MΩ | |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 50 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
100 V (0% to +20%) | Display range | 0.01 to 6.00 MΩ |
Resolution | 0.01 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 6.0 to 60.0 MΩ | |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 60 to 100 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
250 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 250 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 250 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 250 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
500 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 500 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 500 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 500 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
1000 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 600 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 0.6 to 2.0 GΩ | |
Resolution | 100 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(10% + 3 counts) | |
General Specifications | ||
Maximum voltage applied to any terminal and common | 1000 V | |
Storage temperature | -40 °C to 60 °C (-40 °F to 140 °F) | |
Operating temperature | -20 °C to 55 °C (-4 °F to 131 °F) | |
Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F) | |
Relative humidity | Noncondensing | |
0% to 95% @ 10 °C to 30 °C (50 °F to 86 °F) | ||
0% to 75% @ 30 °C to 40 °C (86 °F to 104 °F) | ||
0% to 40% @ 40 °C to 55 °C (104 °F to 131 °F) | ||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | |
Radio frequency communication | 2.4 GHz ISM Band | |
Radio frequency certification | FCC: T68-FBLE, IC: 6627A-FBLE | |
Electromagnetic Compatibility | ||
International | IEC 61326-1:Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A | |
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself. | ||
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. | ||
Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. The equipment may not meet the immunity requirements of this standard when test leads and/or test probes are connected. | ||
Korea (KCC) | Class A Equipment (Industrial Broadcasting & Communication Equipment) | |
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes. | ||
USA (FCC) | 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. | |
Enclosure protection | IEC 60529: IP40 (non-operating) | |
Safety | ||
IEC 61010-1 | Pollution Degree 2 | |
IEC 61010-2-033 | CAT IV 600 V / CAT III 1000 V | |
Batteries | Four AA batteries (NEDA 15A or IEC LR6) | |
Battery life | Meter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. | |
Size (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) | |
Weight | 550 g (1.2 lb) | |
Altitude | Operating | 2000 m |
Storage | 12,000 m | |
Over-range capability | 110% of range except for capacitance which is 100% | |
Frequency overload protection | <107 V Hz | |
Fuse protection for mA input | 0.44A, 1000 V, IR 10 kA |
Description
Fluke 1587 FC Insulation Tester With Fluke Connect
The high-performance 2-in-1 insulation DMM
The Fluke 1587 FC Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter in a single compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.
Fluke 1587 FC Insulation Multimeter Includes:
- Remote probe
- Test leads
- Alligator clips
- K-type thermocouple
- Hard case
- User documentation
The Fluke 1587 FC Insulation Multimeter adds four powerful new diagnostic functions through the Fluke Connect®
Measurements app:
- PI/DAR timed ratio tests with TrendIt™ graphs identifies moisture and contaminated insulation problems faster
- Memory storage through Fluke Connect eliminates writing down results, reduces errors and saves data for historical tracking over time
- Temperature Compensation through app for establishing accurate baselines and relevant historical comparisons
- Historical tracking and trending of assets identifies degradation over time, allows real-time decisions to be made in the field with Fluke Connect® Assets
Product Highlights:
- PI/DAR timed ratio tests
- Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
- VFD low-pass filter for accurate motor drive measurements
- Auto-discharge of capacitive voltage for added user protection
- Insulation test (1587 FC: 0.01 MΩ to 2 GΩ)
- Insulation test voltages (1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V) for many applications
- AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (Ω), Continuity
- Capacitance, diode test, temperature, Min/Max, frequency (Hz)
- Auto power off to save battery power
- CAT III 1000 V, CAT IV 600 V measurement category
- Large display with backlight
- Rugged, utility hard case allows you to bring everything you need for the job
- Included accessories: Remote probe, test leads and probes, alligator clips, K-type thermocouple
- Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient hands free operation
- Three-year standard warranty; extendable to five-years through product registration within 45 days of purchase
Features & Specification
Key Features | AC DC Voltage, Current Measurement, Resistance Measurement, Capacitance Measurement, Continuity Measurement, Memory Function, Test Probe Included, Frequency Measurement, TRMS Measurement | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Product Stock Status | Next Day Delivery (subject to availability) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Manufacturer | Fluke Testers | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short Description |
|
Delivery
Updated January 2024
Please note, our cut-off time is 2:00pm
Orders requiring calibration
Whilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery.
Bank/Public Holidays
Predicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scopeof our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order.
*UK Mainland (Revised March 2021)
Service | Price |
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value OVER £75.00 ex VAT | FREE |
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value UNDER £75.00 ex VAT | £4.95 |
Next WORKING Day (excludes Saturdays, Sundays and public holidays) – UK Mainland only - Zones A & B - ANY order value - Order by 2:00pm | £7.75 |
Saturday ANYTIME Delivery - Order by 2:00pm | £9.95 |
Delivery Surcharges
Because of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:
- Zones A & B - Mainland delivery rates apply.
- Zone C - Scottish Highlands (Charges are calculated at the checkout).
- Zone D - Outer Hebrides, Orkney Isles, Shetland Isles, Isle of Man, Scilly Isles, and Channel Islands (Charges are calculated at the checkout).
- Zone E - Northern Ireland (Charges are calculated at the checkout).
- Zone F - Republic of Ireland (Charges are calculated at the checkout).
Offshore Services
All offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles.
International delivery
International delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk
Export
All export inquiries should be directed to the export division before placement of order.
If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
All stated prices are subject to VAT at the current rate where applicable.
E&OA