Chauvin Arnoux F406 AC-DC TRMS Clamp Meter P01120946

£430.80
Chauvin Arnoux F402 Technical Specification
  F200 SERIES F400 SERIES F600 SERIES
  F201 F203 F205 F402 F404 F406 F407 F604 F606 F607
Ø Clamping diameter 34 mm 48 mm 60 mm
Display LCD Backlit LCD Backlit LCD Backlit LCD
Resolution 6,000 counts 10,000 counts 10,000 counts
Number of values displayed 1 1 3 1 3

Type of aquisition

TRMS [AC] TRMS [AC]/DC TRMS
[AC, AC+DC]/DC
TRMS [AC] TRMS [AC]/DC TRMS
[AC, AC+DC]/DC
TRMS [AC]/DC TRMS
[AC, AC+DC]/DC
Autorange Yes Yes Yes
Automatic AC/DC detection - Yes - Yes Yes
A AC 0.25 to 600 A (900 A peak) 0.25 A to 1,000 A (1,500 A peak) 0.25 A to 2,000 A (3,000 A peak)
A DC - 0.25 A to 900 A - 0.25 A to 1,500 A 0.25 A to 3,000 A
A AC+DC - 0.25 A to 600 A
(900 A peak)
- 0.25 A to 1,000 A
(1,500 A peak)
- 0.25 A to 2000 A
(3,000 A peak)
Best accuracy 1% of reading + 3 counts 1% of reading + 3 counts 1% of reading + 3 counts
V AC 0.15 V to 1,000 V (1,400 V peak) 0.15 V to 1,200 V (1,700 V peak) 0.15 V to 1,000 V
(1,400 V peak)
0.15 V to 1,200 V (1,700 V peak) 0.15 V to 1,000 V
(1,400 V peak)
V DC 0.15 V to 1,000 V 0.15 V to 1,700 V 0.15 V to 1,000 V 0.15 V to 1,700 V 0.15 V to 1,000 V
V AC+DC - 0.15 V to 1,000 V
(1,400 V peak)
- 0.15 V to 1,200 V
(1,700 V peak)
0.15 V to 1,000 V
(1,400 V peak)
- 0.15 V to 1,200 V
(1,700 V peak)
0.15 V to 1,000 V
(1,400 V peak)
Accuracy 1% of reading + 3 counts 1% of reading + 3 counts 1% of reading + 3 counts
Hz Current: 5.0 Hz to 3,000 Hz
Voltage: 5.0 Hz to 20.00 kHz
Current: 5.0 Hz to 2,000 Hz
Voltage: 5.0 Hz to 20.00 kHz
Current: 5.0 Hz to 1,000 Hz
Voltage: 5.0 Hz to 20.00 kHz
Ohm 0.1Ω to 59.99Ω 0.1Ω to 99.99Ω 0.1Ω to 99.99Ω
Open-circuit voltage ≤ 3.6 V ≤ 3.6 V ≤ 3.6 V
Measurement current ≤ 550 µA ≤ 550 µA ≤ 550 µA
Audible continuity Yes Yes Yes
Continuity threshold Adjustable from 1 to 599 W Adjustable from 1 to 999 W 40 W Adjustable from 1 to 999 W 40 W
Diod test (semiconductor function) Yes Yes - Yes -
Temperature (K type) °C: -60.0 to +1,000.0°C
°F: -76.0 to +1,832 °F
- °C: -60.0 to +1,000.0°C
°F: -76.0 to +1,832 °F
- °C: -60.0 to +1,000.0°C
°F: -76.0 to +1,832 °F
-
Single-phase and total three-phase power values - Yes - Yes - Yes
Active power values - 1 W to 600 kW - 1 W to 1,200 kW 1 W to 1,000 kW - 1 W to 2,400 kW 1 W to 2,000 kW
Reactive power values - 1 var to 600 kvar - 1 var to
1,200 kvar
1 var to
1,000 kvar
- 1 var to 2,400 kvar 1 var to 2,000 kvar
Apparent power values - 1 VA to 600 kVA   1 VA to 1200 kVA   - 1 VA to 2,400 kVA 1 VA to 2 000 kVA
PF/DPF - Yes / No - Yes / No Yes / Yes - Yes / No Yes / Yes
Harmonic analysis - Yes - Yes Yes - Yes Yes
THDf / THDr - - / - - Yes / Yes Yes / Yes - Yes / Yes Yes / Yes
Frequential analysis - - - - 25th order - - 25th order
Phase rotation (2-wire method) - Yes - Yes - - Yes -
Function      
True InRush (measurement of overcurrents Yes Yes Yes
Motor startup Yes Yes Yes
Load evolution Yes Yes Yes
Hold Yes Yes Yes
Min/Max Yes Yes Yes
Peak+/Peak- - Yes - Yes - Yes
RELativ ∆X / ∆X/X (%) - Yes / Yes - Yes / Yes - Yes / Yes -
Automatic power-off Yes Yes Yes
Data recording - - Yes - Yes
Communication interface - - Bluetooth - Bluetooth
Ingress protection IP40 IP54 IP54
Electrical safety as per IEC 61010 600V CAT IV 1000V CAT IV / 1500V CAT III 1000V CAT IV 1000V CAT IV / 1500V CAT III 1000V CAT IV
Power supply 1 x 9 V LF22 battery 4 x 1.5 V AA batteries 4 x 1.5 V AA batteries
Dimensions & weight 78 x 222 x 42 mm / 340 g 92 x 272 x 41 mm / 600 g 111 x 296 x 41 mm / 640 g
NEW

Description

Chauvin Arnoux F406 AC-DC TRMS Clamp Meter

*Important Calibration Information: 

This instrument comes with a ‘manufacturer's certificate of conformity’. It is important to understand that this does NOT constitute a ‘traceable calibration certificate’. A certificate of conformity merely states that the equipment has been designed and produced to meet the requirements of its intended application. 
Where calibration of an instrument is possible we will offer this as a separately purchasable item and may be selected from the drop-down box above. You will be sent a full traceable calibration certificate produced in our laboratory and applied with your details as required. 

Overview:

For an electrician, a clamp multimeter is the ideal tool for any work in the field. It is simple to use and groups all the necessary functions in a single, compact solution.
The F200 Series meets the requirements of self-employed electricians and SMIs/SMEs in the electrical sector. For medium and high power values, the
F400 and F600 Series provides maximum protection and safety whatever the measuring conditions and the type of installation.
With its large clamping diameter and current measurements up to 3,000 A, the F600 Series is ideal for distribution and transmission of low-voltage electrical energy.

To deal with the highest level of low-voltage electrical installations, the F400 Series has a high protection rating and is ideal for maintenance, testing, monitoring and diagnostics on medium-power installations.
Equipped with a fast 12-bit TRMS digital acquisition system, F406 clamps offer particularly accurate measurements whatever the signal's waveform.

The Low-Voltage, medium-power F400 Series is used in the LV electricity generation and distribution sectors, industry, railways, etc. It is also suitable for lift/elevator technicians and other lifting or transport equipment specialists.
Maintenance, inspection, monitoring, troubleshooting and connection are the main applications of the clamps in this Series.

          

F406 Clamp Meter Comes Supplied With: 

  • Separate test probes
  • Separate extension leads
  • Batteries
  • Nylon case
  • Crocodile clip

Key Features:

  • Clamping diameter: 48 mm
  • Current: 1,000 A AC / 1,500 ADC
  • Voltage up to 1,200 VAC / 1,700 VDC
  • Resistance and audible continuity
  • Power values (W, var, VA, PF) and Harmonic Distortion (THDf, THDr)
  • "2-wire" phase rotation
  • RELative (ΔX) and Differential measurements (ΔX/X)
  • Diod test
  • Automatic AC/DC detection
  • TrueInrush current measurement
  • Hold, Min, MAX, Peak+ / Peak-
  • CAT IV 1,000 V / CAT III 1,500 V
  • IP54 protection rating

Safe and Rugged

1,000 V CAT IV / 1,500 V CAT III, an unprecedented level of safety for clamp multimeters!
For users, that means the assurance of working in total safety and in compliance with the applicable standards. The IP54 ingress protection protects the instrument against dust, in particular, thus guaranteeing its safety level over time. The mechanical design of these clamps means they can pass
the standard test for falls from a height of 2 metres.

Performance

All the clamps in the F200, F400 and F600 Series benefit from a fast 12-bit TRMS digital acquisition system offering high measurement accuracy.
Thanks to their large bandwidth and high crest factor, these clamps provide accurate measurements whatever the signal type.

Ergonomics

The entire range is designed for one-handed use, even when wearing safety gloves. For maximum efficiency, each measurement corresponds to a specific switch position. The “1 key, 1 function” concept makes it even easier to use.
In addition, all the clamps are equipped with automatic detection of the type of signal (AC or DC) on currents, voltages and power values.

Adapter function

This helps to boost the instrument’s possibilities by using measuring sensors (light meter, I/R temperature, tachometer, etc.) with voltage output (AC or DC). A clever system allows users to read the quantity measured directly.

Phase rotation

To determine the phase order, the use of a 2-wire measuring system with a microprocessor frees users from the constraints and faults encountered with instruments based on resistive or capacitive technology, when using protective accessories (gloves, mat, etc.) or an isolating transformer.

Ripple

The Ripple is a parameter which can be used to quantify the quality of the smoothing in

the case of currents which are rectified and then smoothed. The lower the ripple, the more effective the smoothing. In the

case of a switching power supply, the voltage supplied includes residual ripple, particularly at high frequency. This ripple is harmful for electronic equipment and should be kept to a minimum.

TRMS:

A range equipped with unprecedented functions for analysis and troubleshooting

TRMS versions of Min and Max!
The Min and Max measurements are TRMS values calculated over a duration of up to 100 ms. These values are particularly useful for sizing an installation, the diameter of a supply cable, thermal protection, etc.

Peak+ and Peak-
Calculated over a duration of 1 ms, the Peak+ and Peak- values can be used to characterize the distortions affecting the signal measured. For example, they may reveal variations or even dysfunction in the installation’s behaviour.

THD and Harmonics
When troubleshooting the causes of dysfunction, knowledge of the signal’s distortion, globally (THDr or THDf) or frequentially (harmonic analysis), helps to precisely target the corrective solution required: filtering solution, oversizing, etc.
Harmonic analysis also contributes to the
prevention of fire risks.

∆REL, for a quick assessment
Comparison with a reference quantity is a quick method for assessment and analysis. The variations of a signal can be measured as a differential value or a relative value. Expressed in the unit of the quantity measured, the differential value gives the difference between the stored reference value and the measured value, while the relative value gives a proportion, expressed in %, between this difference and the value of reference. The ΔREL function can be applied to any type of measurement and can be used jointly with the Min, Max and Peak functions.

An Introduction to Chauvin Arnoux's True Inrush Function:

The True Inrush function offers a response to the following issues:

  • Undersizing of the electrical conductors leading to heating, premature ageing of the insulants, potentially causing short-circuits or fires of electrical origin.
  • Untimely tripping of the thermal protective systems causing malfunctions, faults or lost productivity

Because the True inrush function is more than just a means of measuring the inrush current when a motor starts up, as it also allows analysis of the overcurrents at any point in an electrical installation in operation. Present on all the models in the F200, F400 and F600 Series, the True Inrush function adapts its algorithm to suit the nature and level of the current present in the installation to enable the capture of the expected overcurrent.
The True Inrush function can be used to check that electrical installations are correctly sized in terms of both the conductors used and the protective systems implemented to reduce the risks.
The True Inrush function contributes to safety, maintenance and optimization of the operating costs of electrical installations.

isswww and Chauvin Arnoux

The Chauvin Arnoux Group of companies, incorporating the Metrix and Multimetrix brands are synonymous with design and production of the finest quality products for the electrical testing industry, covering a diverse sector of the market for over 100 years. From their awarded Digiflex current sensors, universal testers, multimeters, network and power analysers, right up to laboratory instrumentation and beyond.  

isswww and Chauvin Arnoux have enjoyed a close working partnership for many years and we supply many of their products to trade and industry the world over. 

Features & Specification

More Information
Key Features Jaw Capacity 48mm dia, Voltage up to 1200 VAC / 1700 VDC, Resistance and audible continuity, Automatic AC/DC detection, TrueInrush current measurement, CAT IV 1000 V / CAT III 1500 V, Hold/Min/Max, Current: 1000A AC / 1500A DC, Power values (W var VA PF), Harmonic Distortion (THDf THDr)
Manufacturer Chauvin Arnoux
Short Description
Chauvin Arnoux F402 Technical Specification
  F200 SERIES F400 SERIES F600 SERIES
  F201 F203 F205 F402 F404 F406 F407 F604 F606 F607
Ø Clamping diameter 34 mm 48 mm 60 mm
Display LCD Backlit LCD Backlit LCD Backlit LCD
Resolution 6,000 counts 10,000 counts 10,000 counts
Number of values displayed 1 1 3 1 3

Type of aquisition

TRMS [AC] TRMS [AC]/DC TRMS
[AC, AC+DC]/DC
TRMS [AC] TRMS [AC]/DC TRMS
[AC, AC+DC]/DC
TRMS [AC]/DC TRMS
[AC, AC+DC]/DC
Autorange Yes Yes Yes
Automatic AC/DC detection - Yes - Yes Yes
A AC 0.25 to 600 A (900 A peak) 0.25 A to 1,000 A (1,500 A peak) 0.25 A to 2,000 A (3,000 A peak)
A DC - 0.25 A to 900 A - 0.25 A to 1,500 A 0.25 A to 3,000 A
A AC+DC - 0.25 A to 600 A
(900 A peak)
- 0.25 A to 1,000 A
(1,500 A peak)
- 0.25 A to 2000 A
(3,000 A peak)
Best accuracy 1% of reading + 3 counts 1% of reading + 3 counts 1% of reading + 3 counts
V AC 0.15 V to 1,000 V (1,400 V peak) 0.15 V to 1,200 V (1,700 V peak) 0.15 V to 1,000 V
(1,400 V peak)
0.15 V to 1,200 V (1,700 V peak) 0.15 V to 1,000 V
(1,400 V peak)
V DC 0.15 V to 1,000 V 0.15 V to 1,700 V 0.15 V to 1,000 V 0.15 V to 1,700 V 0.15 V to 1,000 V
V AC+DC - 0.15 V to 1,000 V
(1,400 V peak)
- 0.15 V to 1,200 V
(1,700 V peak)
0.15 V to 1,000 V
(1,400 V peak)
- 0.15 V to 1,200 V
(1,700 V peak)
0.15 V to 1,000 V
(1,400 V peak)
Accuracy 1% of reading + 3 counts 1% of reading + 3 counts 1% of reading + 3 counts
Hz Current: 5.0 Hz to 3,000 Hz
Voltage: 5.0 Hz to 20.00 kHz
Current: 5.0 Hz to 2,000 Hz
Voltage: 5.0 Hz to 20.00 kHz
Current: 5.0 Hz to 1,000 Hz
Voltage: 5.0 Hz to 20.00 kHz
Ohm 0.1Ω to 59.99Ω 0.1Ω to 99.99Ω 0.1Ω to 99.99Ω
Open-circuit voltage ≤ 3.6 V ≤ 3.6 V ≤ 3.6 V
Measurement current ≤ 550 µA ≤ 550 µA ≤ 550 µA
Audible continuity Yes Yes Yes
Continuity threshold Adjustable from 1 to 599 W Adjustable from 1 to 999 W 40 W Adjustable from 1 to 999 W 40 W
Diod test (semiconductor function) Yes Yes - Yes -
Temperature (K type) °C: -60.0 to +1,000.0°C
°F: -76.0 to +1,832 °F
- °C: -60.0 to +1,000.0°C
°F: -76.0 to +1,832 °F
- °C: -60.0 to +1,000.0°C
°F: -76.0 to +1,832 °F
-
Single-phase and total three-phase power values - Yes - Yes - Yes
Active power values - 1 W to 600 kW - 1 W to 1,200 kW 1 W to 1,000 kW - 1 W to 2,400 kW 1 W to 2,000 kW
Reactive power values - 1 var to 600 kvar - 1 var to
1,200 kvar
1 var to
1,000 kvar
- 1 var to 2,400 kvar 1 var to 2,000 kvar
Apparent power values - 1 VA to 600 kVA   1 VA to 1200 kVA   - 1 VA to 2,400 kVA 1 VA to 2 000 kVA
PF/DPF - Yes / No - Yes / No Yes / Yes - Yes / No Yes / Yes
Harmonic analysis - Yes - Yes Yes - Yes Yes
THDf / THDr - - / - - Yes / Yes Yes / Yes - Yes / Yes Yes / Yes
Frequential analysis - - - - 25th order - - 25th order
Phase rotation (2-wire method) - Yes - Yes - - Yes -
Function      
True InRush (measurement of overcurrents Yes Yes Yes
Motor startup Yes Yes Yes
Load evolution Yes Yes Yes
Hold Yes Yes Yes
Min/Max Yes Yes Yes
Peak+/Peak- - Yes - Yes - Yes
RELativ ∆X / ∆X/X (%) - Yes / Yes - Yes / Yes - Yes / Yes -
Automatic power-off Yes Yes Yes
Data recording - - Yes - Yes
Communication interface - - Bluetooth - Bluetooth
Ingress protection IP40 IP54 IP54
Electrical safety as per IEC 61010 600V CAT IV 1000V CAT IV / 1500V CAT III 1000V CAT IV 1000V CAT IV / 1500V CAT III 1000V CAT IV
Power supply 1 x 9 V LF22 battery 4 x 1.5 V AA batteries 4 x 1.5 V AA batteries
Dimensions & weight 78 x 222 x 42 mm / 340 g 92 x 272 x 41 mm / 600 g 111 x 296 x 41 mm / 640 g
Product Stock Status Next Day Delivery (subject to availability)

Delivery

Updated January 2024

Please note, our cut-off time is 2:00pm

Orders requiring calibration 

Whilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.
Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery.

Bank/Public Holidays

Predicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scope
of our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order.

*UK Mainland (Revised March 2021)

Service Price
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value OVER £75.00 ex VAT FREE
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value UNDER £75.00 ex VAT £4.95
Next WORKING Day (excludes Saturdays, Sundays and public holidays)  – UK Mainland only - Zones A & B  - ANY order value - Order by 2:00pm £7.75
Saturday ANYTIME Delivery - Order by 2:00pm £9.95
 

 

 

 

 

Delivery Surcharges

Because of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:

  • Zones A & B  - Mainland delivery rates apply. 
  • Zone C - Scottish Highlands (Charges are calculated at the checkout).
  • Zone D - Outer Hebrides, Orkney Isles, Shetland Isles, Isle of Man, Scilly Isles, and Channel Islands (Charges are calculated at the checkout).
  • Zone E - Northern Ireland (Charges are calculated at the checkout).
  • Zone F - Republic of Ireland (Charges are calculated at the checkout).

Offshore Services

All offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles.

International delivery

International delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk

Export 

All export inquiries should be directed to the export division before placement of order.

If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
All stated prices are subject to VAT at the current rate where applicable.
E&OA