Chauvin Arnoux CA 8345 Power Analyser P01160657
Chauvin Arnoux CA8345 Qualistar Power Quality Analyser
Technical Specifications:
Inputs | Voltage/current, isolated |
Voltage | 5 V to 1,000 vAC and vDC |
IEC 61000-4-30 (Ed 3) | Class A (Full) |
Screen | 7" colour LCD touch screen: 800 x 480 (WVGA) |
Clock/GPS | Yes, built-in |
Real-time mode | Yes |
Sampling rate | Voltage 400kSps / Current 200kSps / Surge 2MSps |
Power mode | Yes |
Energy mode | Yes |
Unbalance mode | Composite |
Harmonics mode | DC to 63rd order |
Interharmonics mode | 0 to 62nd order |
Trend recording | > 900 parameters |
Alarm mode (types / number) | 52 / 20,000 |
Carrier current detection mode | Yes |
Inrush capture (number) | 100 |
2.5 µs transients (number) | No maximum (SD card) |
Shockwaves | Up to 12 kV sampled every 500ns |
EN50160 monitoring mode | With PAT3 software |
USB communication | Yes |
SD card | Accessible, external |
Ethernet | Yes |
Wi-fi | Yes |
Web Server | Yes |
USB key port (Type A) | Yes |
Battery cartridge | Li-ion – 5800 Ah |
IEC 61010 safety | CAT IV 1000V |
Protection | IP54 |
Operating temperature | [+0 °C; +40 °C] |
Environmental compliance | IEC 61557-12 & IEC 62586 |
Dimensions (H x L x D) | 200x285x55 mm / 1.9 kg |
Description
Chauvin Arnoux CA8345 Power Analyser P01160657
CA8345 Comes Supplied With:
• Safety datasheet
• 5 reeling boxes
• Shoulder bag
• USB A/B cable 1.80 m long
• Multilingual Quick Start Guide
• Set of 5 banana leads and crocodile clips
• Set of identification inserts and rings
• Verification certificate
• Removable wrist strap
• Magnetic hook
• SD memory card
*Important Calibration Information:
This instrument comes with a ‘manufacturer's certificate of conformity’ It is important to understand that this does NOT constitute a ‘calibration certificate’. A certificate of conformity merely states that the equipment has been designed and produced to meet the requirements of its intended application.
Where calibration of an instrument is possible we will offer this as a separately purchasable item and may be selected from the drop-down box above. You will be sent a full traceable calibration certificate produced in our laboratory and applied with your details as required.
The CA 8345 is a Class A Qualistar power and energy quality analyser.
Like the Qualistar+ models, it is equipped with an intuitive HMI and remains simple to use. Multilingual online help can be displayed at any time on the large colour LCD touch screen.
Easy to handle, it is intended for inspection and maintenance teams working on industrial or tertiary installations. It can be used to obtain a snapshot of the electrical network's main quality features. The Qualistar model can be used on all types of installations.
For greater safety, the CA 8345 automatically recognizes the type of current sensor connected.
The CA 8345 ensures high measurement accuracy. It provides a large number of calculated values and several processing functions. It offers users all the measurements needed to successfully handle energy efficiency projects and monitor the electrical distribution network. By calculating the cost of the electricity, you can immediately determine the value of the electricity consumed.
Key Features:
- Voltage quality diagnostics
- Full compliance with IEC 61000-4-30 Class A Ed 3
- Highly communicating instrument
- Qualistar range of easy-to-use products
- Alarms, recordings, transients, Inrush, etc.
It can display the harmonics and interharmonics as stipulated by IEC 61000-4-7.
At the same time, it detects the carrier currents flowing on the installation.
The CA 8345 monitors all the events on the network:
- Trend diagram, variations of the signal parameters
- Parameterizable alarms, with the possibility of sending an email alert to the user
- 2.5 µs transients
- 12 kV shockwaves lasting 500 ns
- TrueInrush to capture all the load start-ups….
A Monitoring mode can be used to record the measurement campaigns required for analysis as per EN50160.
Communication
In addition to the SD and USB drive, it is also possible to recover the measurements and communicate with the CA 8345 remotely. USB, remote links, Wifi (direct or via server) or via RJ45. An IRD Server mode allows extraction of the data from anywhere in the world without endangering internet security.
The Power Analyzer Transfer software can be used to process the measurements made with the Qualistar Class A.
The PAT3 software can be downloaded from our Support website.
General
• Portable energy quality anaylser
• Instrument compliant with IEC 61000-4-30 edition 3.0 Class A for all functions
• Measurements on all installation types: three-phase, Aron connection, etc.
• Electrical network monitoring with the setting of alarms
• IP54 casing 55 mm thick with stand
• IEC 61010 CAT IV 1000 V
• Parameterization with software for EN 50160 reports
Measurements
• All DC components are taken into account
• Harmonics (amplitude and phase shift) from DC to the 63rd order
• Inter-harmonic subgroups from 0 to the 62nd order
• 2 carrier current frequencies monitored
• Measurement of P, N, Q1
, S and D power values (total and per phase)
• Measurement of energy values (total and per phase) with Energy valuation
• Internal GPS for precise UTC synchronization (NTP possible too)
Communication
• USB 2.0 external flash drive supported (host devices)
• USB 2.0 connection with a PC
• Ethernet 100 Mbps communication
• Wi-Fi 802.11b/g communication
• Webserver for a remote user interface with Android,
Microsoft and iOS applications
• Backup and recording of screenshots (image and data)
• Recording and export to a PC
• Software for real-time data recovery and communication with a PC
Ergonomics
• Wide 7-inch colour LCD touch screen (WVGA)
• Real-time display of waveforms (4 voltage and 4 current)
• DC current sensor power supply
• 5 x 50 Hz/60 Hz AC/DC voltage inputs
• User-friendly, multlingual GUI
• Intuitive use
• User profiles
• Fully multi-task instrument
• Automatic recognition of different current sensors
• Display of phasor diagrams
• Waveforms at 512 samples per cycle, with Min/Max 2.5µs
• Real-time waveforms displayed from 1 cycle to 10/12 cycles
Calculations
• Calculation of K factor & FHL
• Calculation of distorting voltages and currents
• Calculation of Displacement Power Factor (DPF) and Power Factor (PF)
• Calculation of Pst & Plt flicker and the sliding Pst
• Calculation of unbalance (current and voltage)
• Waveform Inrush with a duration of 10 minutes
• RMS and Peak Inrush for up to 30 minutes
• Capture of hundreds of 2.5 µs transients
• Capture shockwaves up to 12kV with a resolution of 500ns
• Recording of trends
• Trend recording period from 200 ms to 2 hrs
isswww and Chauvin Arnoux
The Chauvin Arnoux Group of companies, incorporating the Metrix and Multimetrix brands are synonymous with the design and production of the finest quality products for the electrical testing industry, covering a diverse sector of the market for over 100 years. From their awarded Digiflex current sensors, universal testers, multimeters, network and power analysers, right up to laboratory instrumentation and beyond.
isswww and Chauvin Arnoux have enjoyed a close working partnership for many years and we supply many of their products to trade and industry the world over.
Features & Specification
Key Features | Voltage quality diagnostics, Full compliance with IEC 61000-4-30 Class A , Easy to use, Fully Downloadable, Trend recording period from 200 ms to 2 hrs, Recording of trends, Calculation of unbalance (current and voltage), Calculation of Displacement Power Factor (DPF) and Power Factor (PF) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Product Stock Status | Next Day Delivery (subject to availability) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Manufacturer | Chauvin Arnoux | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Short Description | Chauvin Arnoux CA8345 Qualistar Power Quality Analyser
|
Inputs | Voltage/current, isolated |
Voltage | 5 V to 1,000 vAC and vDC |
IEC 61000-4-30 (Ed 3) | Class A (Full) |
Screen | 7" colour LCD touch screen: 800 x 480 (WVGA) |
Clock/GPS | Yes, built-in |
Real-time mode | Yes |
Sampling rate | Voltage 400kSps / Current 200kSps / Surge 2MSps |
Power mode | Yes |
Energy mode | Yes |
Unbalance mode | Composite |
Harmonics mode | DC to 63rd order |
Interharmonics mode | 0 to 62nd order |
Trend recording | > 900 parameters |
Alarm mode (types / number) | 52 / 20,000 |
Carrier current detection mode | Yes |
Inrush capture (number) | 100 |
2.5 µs transients (number) | No maximum (SD card) |
Shockwaves | Up to 12 kV sampled every 500ns |
EN50160 monitoring mode | With PAT3 software |
USB communication | Yes |
SD card | Accessible, external |
Ethernet | Yes |
Wi-fi | Yes |
Web Server | Yes |
USB key port (Type A) | Yes |
Battery cartridge | Li-ion – 5800 Ah |
IEC 61010 safety | CAT IV 1000V |
Protection | IP54 |
Operating temperature | [+0 °C; +40 °C] |
Environmental compliance | IEC 61557-12 & IEC 62586 |
Dimensions (H x L x D) | 200x285x55 mm / 1.9 kg |
Delivery
Updated January 2024
Please note, our cut-off time is 2:00pm
Orders requiring calibration
Whilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery.
Bank/Public Holidays
Predicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scopeof our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order.
*UK Mainland (Revised March 2021)
Service | Price |
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value OVER £75.00 ex VAT | FREE |
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value UNDER £75.00 ex VAT | £4.95 |
Next WORKING Day (excludes Saturdays, Sundays and public holidays) – UK Mainland only - Zones A & B - ANY order value - Order by 2:00pm | £7.75 |
Saturday ANYTIME Delivery - Order by 2:00pm | £9.95 |
Delivery Surcharges
Because of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:
- Zones A & B - Mainland delivery rates apply.
- Zone C - Scottish Highlands (Charges are calculated at the checkout).
- Zone D - Outer Hebrides, Orkney Isles, Shetland Isles, Isle of Man, Scilly Isles, and Channel Islands (Charges are calculated at the checkout).
- Zone E - Northern Ireland (Charges are calculated at the checkout).
- Zone F - Republic of Ireland (Charges are calculated at the checkout).
Offshore Services
All offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles.
International delivery
International delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk
Export
All export inquiries should be directed to the export division before placement of order.
If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
All stated prices are subject to VAT at the current rate where applicable.
E&OA