Fluke 1738EU Three Phase Power Logger Advanced Model

Special Price £5,548.80 Regular Price £6,657.60
Specifications
Accuracy
Parameter Range Resolution Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale)
Voltage 1000 V 0.1 V ±(0.2% + 0.01%)
Current: Direct input i17xx-flex 1500 12" 150 A 0.1 A ±(1% + 0.02%)
1500 A 1 A
i17xx-flex 3000 24" 300 A 1 A ±(1% + 0.03%)
3000 A 10 A
i17xx-flex 6000 36" 600 A 1 A ±(1.5% + 0.03%)
6000 A 10 A
i40s-EL clamp 4 A 1 mA ±(0.7% + 0.02%)
40 A 10 mA
Frequency 42.5 Hz to 69 Hz 0.01 Hz ±(0.1%)
Auxillary input ±10 V dc 0.1 mV ±(0.2% + 0.02%)
Voltage min/max 1000 V 0.1 V ±(1% + 0.1%)
Current min/max Defined by accessory Defined by accessory ±(5% + 0.2%)
THD on voltage 1000% 0.1% ±0.5
THD on current 1000% 0.1% ±0.5
Voltage harmonics 2nd to 50th 1000 V 0.1 V ≥ 10 V: ±5% of reading
< 10 V: ±0.5V
Current harmonics 2nd to 50th Defined by accessory Defined by accessory ≥ 3% of current range: ±5% of reading
< 3% of current range: ±0.15% of range
Unbalance 100% 0.1% ±0.2
Intrinsic Uncertainty ±(% of reading +% of range)¹
Parameter Influence quantity iFlex1500-12 iFlex3000-24 iFlex6000-36 i40S-EL
150 A / 1500 A 300 A / 3000 A 600 A / 6000 A 4 A / 40 A
Active Power P  PF ≥ 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Active Energy Ea
Apparent power S 0 ≤ PF ≤ 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent Energy Eap
Reactive power Q 0 ≤ PF ≤ 1 2.5% of measured apparent power
Reactive Energy Er
Power Factor PF - ±0.025
Displacement Power Factor
DBF/cosϕ
Additional uncertainty in% of range¹ VP-N>250 V 0.015% 0.0225% 0.0225% 0.015%
¹Range = 1000 V x Irange
Reference conditions:
  • Environmental: 23 °C ±5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65%
  • Input conditions: Cosϕ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10%.
  • Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10% of Irange
  • Primary conductor of clamps or Rogowski coil in center position
  • Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C

 

Electrical Specifications
Power Supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency ≥ 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ±15%
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime Four hours in standard operating mode, up to 5.5 hours in power saving mode
Charging time < 6 hours
Data Acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
Data storage Internal flash memory (not user replaceable)
Memory size Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
¹The number of possible logging sessions and logging period depends on user requirements.
Basic Interval
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
Averaging interval 10 min
Individual harmonics 2nd to 50th harmonic
Total harmonic distortion Calculated on 50 harmonics
Events Voltage: dips, swells, interruptions, current: inrush current
Triggered recordings Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
Waveform of voltage and current
Standards Compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time harmonics)
Power quality IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power IEEE 1459
Power quality compliance EN50160 (for measured parameters)
Interfaces
USB-A File transfer via USB flash drive, firmware updates 
Max. current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
USB-mini Data download device to PC
Voltage Inputs
Number of inputs 4 (3 phases and neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth (-3 dB) 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Current Inputs
Number of inputs 4, mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Range 1 A to 150 A / 10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
3 A to 300 A / 30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
6 A to 600 A / 60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
40 mA to 4 A / 0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB) 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Auxiliary Inputs
Number of inputs 2
Input range 0 to ±10 V dc, 1reading/s
Scale factor (available 2014) Format: mx + b (gain and offset) user configurable
Displayed units (available 2014) User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Connection
Number of inputs 2
Supported modules Fluke Connect® 3000 series
Acquisition 1 reading/s
Environmental Specifications
Operating temperature -10 °C to +50 °C (14 °F to 122 °F)
Storage temperature -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity 10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000m
Enclosure IP50 in accordance with EN60529
Vibration MIL-T-28800E, Type 3, Class III, Style B
Safety IEC 61010-1
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibility EN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Temperature coefficient 0.1 x accuracy specification/°C
General Specifications
Color LCD display 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty Instrument and power supply: Two-years (battery not included) 
Accessories: one-year 
Calibration cycle: two-years 
Dimensions Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
Weight Instrument: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb)
Tamper protection Kensington lock slot
i17xx-flex 1500 12" Flexible Current Probe Specifications
Measuring range 1 to 150 A ac/10 to 1500 A ac
Nondestructive current 100 kA (50/60 Hz)
Intrinsic error at reference condition* ±0.7% of reading
Accuracy 173x + iFlex ±(1% of reading + 0.02% of range)
Temperature coefficient over operating temperature range 0.05% of reading/°C 0.09% of reading/°F
Working voltage 1000 V CAT III, 600 V CAT IV
Probe cable length 305 mm (12 in)
Probe cable diameter 7.5 mm (0.3 in)
Minimum bending radius 38 mm (1.5 in)
Output cable length 2 m (6.6 ft)
Weight 115 g
Probe cable material TPR
Coupling material POM + ABS/PC
Output cable TPR/PVC
Operating temperature -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating 15% to 85% non-condensing
IP rating IEC 60529:IP50
Warranty One-year
* Reference condition:
  • Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65%
  • Primary conductor in center position

Description

Fluke 1738/EU Three-Phase Power Quality Logger (Advanced)

The Fluke 1738/EU Three-phase Power Quality Logger is a versatile, three-phase Fluke Connect-compatible power logger for conducting energy, load and power quality studies.

 

The three-phase power logger with the mobile app and desktop software Fluke Connect® is compatible, offers you the data you need to make informed decisions for the optimisation of power quality and energy consumption. As the ideal measuring instrument for energy studies and basic power quality logging records and logs the Power Logger automatically supply quality parameters, so that you get more insight into the data and both the reliability of the system as well as the savings can optimize.


Fluke 1738/EU Comes Supplied With:

  • WiFi and BLE adapter
  • USB Flash Drive (4GB)
  • USB Cable
  • 43PHVL-173 Flat Cable
  • 1x red, 1x black 0.1m cable
  • 1x1x red, 1x black 1.5m cable
  • 4 Alligator clips
  • C173x Soft Case
  • Colour Coding Set
  • 173x-Hanger kit
  • MP1-Magnet Probe
  • i173X-flex1500 12"
  • i173x-Flex1500 12"
  • Line cord EU US UK


 

Log the most common parameters

Designed to measure the most critical three phase power parameters, the 1738 can simultaneously log RMS voltage, RMS current, voltage and current events, voltage and current THD, voltage and current harmonics up to the 50th harmonic, active power, reactive power, power factor, active energy, reactive energy, and more. With enough memory for more than a year of data logging, the 1738 can uncover intermittent or hard-to-find issues that might otherwise have been missed.

Analysis and Reporting

Capturing logged data is just one part of the task. Once you have the data, you need to create useful information and reports that can be easily shared and understood by your organization or customers. Fluke Energy Analyze Plus software makes that task as simple as possible. With powerful analysis tools and the ability to create customized reports in minutes you’ll be able to communicate your findings and quickly solve problems so you can optimize system reliability and savings.

Key Features:

The Fluke 1738 Three-phase Power Quality Logger is a versatile, three-phase Fluke Connect-compatible power logger for conducting energy, load and power quality studies.

  • Key measurements: Automatically capture and log voltage, current, power, harmonics and associated power quality values, and capture dips, swells, and inrush currents with event waveform snapshots and high-resolution RMS profiles
  • Convenient instrument powering: Power instrument directly from the measured circuit
  • Energy Analyze Plus application software: Download and analyze every detail of energy consumption and power quality state of health with our automated reporting and use the integrated power quality health summary to get an at-a-glance understanding of system health

 

Other useful features:

  • Present data locally on the logger, on the Fluke Connect mobile app and desktop software, or through your facility’s Wi-Fi infrastructure
  • Measure all three phases and neutral with four flexible current probes (included)
  • Power the instrument directly from the measured circuit
  • Review measured values during logging sessions and before downloading for real-time analysis
  • Includes event waveform snapshot and high-resolution RMS profile with the 1738, along with date, timestamp and severity to capture dips, swells, and inrush currents and help pinpoint potential root causes of power quality issues
  • 1738 also provides fast insight into overall electrical system health with a Power Quality Health Summary
  • Offers a bright, color touch-screen display for convenient field analysis and data checks
  • Helps you capture the right data every time with a quick, guided, graphical user interface
  • Reduces uncertainty about your connections with the intelligent verification function
  • Allows you to complete field setups through the front panel or the Fluke Connect App on your smartphone
  • Provides fully integrated logging with other Fluke Connect-enabled devices to simultaneously log up to two additional measurement parameters on a Fluke Connect wireless digital multimeter or module*
  • Comes with Energy Analyze Plus application software that enables you to analyze every detail of energy consumption and power quality health and create automated reports

 

isswww and Fluke Instruments

Fluke Corporation is the world leader in the manufacture, distribution and service of electronic test tools and software.

Since its founding in 1948, Fluke has helped define and grow a unique technology market, providing testing and troubleshooting capabilities that have grown to status in manufacturing and service industries. Every new manufacturing plant, office, hospital, or facility built today represents another potential customer for Fluke products.

From industrial electronic installation, maintenance and service, to precision measurement and quality control, Fluke tools help keep business and industry around the globe up and running. Typical customers and users include technicians, engineers, meteorologists, medical-device manufacturers, and computer network professionals, people who stake their reputations on their tools, and use tools to help extend their personal power and abilities.

Fluke are a founding core supplier of ISSWWW and we enjoy a personal and professional relationship with them. Our sales staff and our technicians are Fluke trained and we hold perhaps the largest stock of their products in the country. Our customers know that when it comes to Fluke products, we have not only the best prices but the best advice and support services, reassuring when you need to make that all-important purchase.

Features & Specification

More Information
Key Features 600 V CAT IV/1000 V CAT III, Capture and log voltage, Complete with 12" probes, Conduct load studies, Data Storage, Measure power factor, Power from measured circuits, Wi-fi enabled
Product Stock Status Next Day Delivery (subject to availability)
Manufacturer Fluke Testers
Short Description
Specifications
Accuracy
Parameter Range Resolution Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale)
Voltage 1000 V 0.1 V ±(0.2% + 0.01%)
Current: Direct input i17xx-flex 1500 12" 150 A 0.1 A ±(1% + 0.02%)
1500 A 1 A
i17xx-flex 3000 24" 300 A 1 A ±(1% + 0.03%)
3000 A 10 A
i17xx-flex 6000 36" 600 A 1 A ±(1.5% + 0.03%)
6000 A 10 A
i40s-EL clamp 4 A 1 mA ±(0.7% + 0.02%)
40 A 10 mA
Frequency 42.5 Hz to 69 Hz 0.01 Hz ±(0.1%)
Auxillary input ±10 V dc 0.1 mV ±(0.2% + 0.02%)
Voltage min/max 1000 V 0.1 V ±(1% + 0.1%)
Current min/max Defined by accessory Defined by accessory ±(5% + 0.2%)
THD on voltage 1000% 0.1% ±0.5
THD on current 1000% 0.1% ±0.5
Voltage harmonics 2nd to 50th 1000 V 0.1 V ≥ 10 V: ±5% of reading
< 10 V: ±0.5V
Current harmonics 2nd to 50th Defined by accessory Defined by accessory ≥ 3% of current range: ±5% of reading
< 3% of current range: ±0.15% of range
Unbalance 100% 0.1% ±0.2
Intrinsic Uncertainty ±(% of reading +% of range)¹
Parameter Influence quantity iFlex1500-12 iFlex3000-24 iFlex6000-36 i40S-EL
150 A / 1500 A 300 A / 3000 A 600 A / 6000 A 4 A / 40 A
Active Power P  PF ≥ 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Active Energy Ea
Apparent power S 0 ≤ PF ≤ 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent Energy Eap
Reactive power Q 0 ≤ PF ≤ 1 2.5% of measured apparent power
Reactive Energy Er
Power Factor PF - ±0.025
Displacement Power Factor
DBF/cosϕ
Additional uncertainty in% of range¹ VP-N>250 V 0.015% 0.0225% 0.0225% 0.015%
¹Range = 1000 V x Irange
Reference conditions:
  • Environmental: 23 °C ±5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65%
  • Input conditions: Cosϕ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10%.
  • Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V Input current: I > 10% of Irange
  • Primary conductor of clamps or Rogowski coil in center position
  • Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C

 

Electrical Specifications
Power Supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency ≥ 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ±15%
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime Four hours in standard operating mode, up to 5.5 hours in power saving mode
Charging time < 6 hours
Data Acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
Data storage Internal flash memory (not user replaceable)
Memory size Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
¹The number of possible logging sessions and logging period depends on user requirements.
Basic Interval
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
Averaging interval 10 min
Individual harmonics 2nd to 50th harmonic
Total harmonic distortion Calculated on 50 harmonics
Events Voltage: dips, swells, interruptions, current: inrush current
Triggered recordings Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
Waveform of voltage and current
Standards Compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time harmonics)
Power quality IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power IEEE 1459
Power quality compliance EN50160 (for measured parameters)
Interfaces
USB-A File transfer via USB flash drive, firmware updates 
Max. current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
USB-mini Data download device to PC
Voltage Inputs
Number of inputs 4 (3 phases and neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth (-3 dB) 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Current Inputs
Number of inputs 4, mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Range 1 A to 150 A / 10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
3 A to 300 A / 30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
6 A to 600 A / 60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
40 mA to 4 A / 0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB) 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Auxiliary Inputs
Number of inputs 2
Input range 0 to ±10 V dc, 1reading/s
Scale factor (available 2014) Format: mx + b (gain and offset) user configurable
Displayed units (available 2014) User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Connection
Number of inputs 2
Supported modules Fluke Connect® 3000 series
Acquisition 1 reading/s
Environmental Specifications
Operating temperature -10 °C to +50 °C (14 °F to 122 °F)
Storage temperature -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity 10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000m
Enclosure IP50 in accordance with EN60529
Vibration MIL-T-28800E, Type 3, Class III, Style B
Safety IEC 61010-1
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibility EN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Temperature coefficient 0.1 x accuracy specification/°C
General Specifications
Color LCD display 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty Instrument and power supply: Two-years (battery not included) 
Accessories: one-year 
Calibration cycle: two-years 
Dimensions Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
Weight Instrument: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb)
Tamper protection Kensington lock slot
i17xx-flex 1500 12" Flexible Current Probe Specifications
Measuring range 1 to 150 A ac/10 to 1500 A ac
Nondestructive current 100 kA (50/60 Hz)
Intrinsic error at reference condition* ±0.7% of reading
Accuracy 173x + iFlex ±(1% of reading + 0.02% of range)
Temperature coefficient over operating temperature range 0.05% of reading/°C 0.09% of reading/°F
Working voltage 1000 V CAT III, 600 V CAT IV
Probe cable length 305 mm (12 in)
Probe cable diameter 7.5 mm (0.3 in)
Minimum bending radius 38 mm (1.5 in)
Output cable length 2 m (6.6 ft)
Weight 115 g
Probe cable material TPR
Coupling material POM + ABS/PC
Output cable TPR/PVC
Operating temperature -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating 15% to 85% non-condensing
IP rating IEC 60529:IP50
Warranty One-year
* Reference condition:
  • Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65%
  • Primary conductor in center position

Delivery

Updated January 2024

Please note, our cut-off time is 2:00pm

Orders requiring calibration 

Whilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.
Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery.

Bank/Public Holidays

Predicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scope
of our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order.

*UK Mainland (Revised March 2021)

Service Price
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value OVER £75.00 ex VAT FREE
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value UNDER £75.00 ex VAT £4.95
Next WORKING Day (excludes Saturdays, Sundays and public holidays)  – UK Mainland only - Zones A & B  - ANY order value - Order by 2:00pm £7.75
Saturday ANYTIME Delivery - Order by 2:00pm £9.95
 

 

 

 

 

Delivery Surcharges

Because of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:

  • Zones A & B  - Mainland delivery rates apply. 
  • Zone C - Scottish Highlands (Charges are calculated at the checkout).
  • Zone D - Outer Hebrides, Orkney Isles, Shetland Isles, Isle of Man, Scilly Isles, and Channel Islands (Charges are calculated at the checkout).
  • Zone E - Northern Ireland (Charges are calculated at the checkout).
  • Zone F - Republic of Ireland (Charges are calculated at the checkout).

Offshore Services

All offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles.

International delivery

International delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk

Export 

All export inquiries should be directed to the export division before placement of order.

If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
All stated prices are subject to VAT at the current rate where applicable.
E&OA