Megger TDR500-3 TDR Time Domain Reflectometer
Megger TDR500/3 Time Domain Reflectometer | |
Ranges | 10 m, 25 m, 100 m, 250 m, 1000 m, 2500 m, 5000 m (30 ft, 75 ft, 300 ft, 750 ft, 3000 ft, 7500 ft, 15000 ft) |
Accuracy | ±1% of range ± pixel at 0.67 VF [Note- The measurement accuracy is for the indicated cursor position only and is conditional on the velocity factor being correct.] |
Resolution | 1% of range |
Input Protection | This instrument complies with IEC61010-1 for connection to live systems up to 150V CAT IV when used with the optional fused test lead set |
Output Pulse | 5V peak to peak into open circuit. Pulse widths determined by range and cable |
Gain | Set for each range with three user-selectable steps (in manual operation mode) |
Velocity Factor | Variable from 0.2 to 0.99 in steps of 0.01 |
TX Null | Automatic |
Power Down | Automatic after 5 mins with no keys pressed |
Backlight | Stays on for 1 minute with no keys pressed |
Batteries | 5 x LR6 (AA) batteries, manganese alakli or nickel metal-hydride cells |
Battery Life | Up to 14 hours (typical) |
Dimensions | 230mm x 115mm x 48mm |
Weight | 0.6kg |
Description
Megger TDR500/3Time Domain Reflector 1002-227
The TDR500/3 is a handheld, compact Time Domain Reflectometer for locating faults on metallic cables. It has a minimum resolution of 0.1 m/0.3 ft and a 5 km/15 kft maximum range depending on velocity factor selected and cable type. Four output impedances are available (25, 50, 75, and 100 Ω) and a velocity factor between 0.2 and 0.99 will meet any cable test requirements The TDR500/3 has a simple selection option which together with a 4 way control switch offers an intuitive operation for the user.
Key Features:
- Simple operation.
- AUTO selection of gain and pulse width.
- Ultra fast pulse for near end fault identification.
- Trace HOLD feature.
- IP54 rating offers real life working.
- Designed for use on all metallic cable pairs.
- Backlit graphics monochrome LCD (256 x 128)
- Adjustable display contrast
- Resolution to 0.1 m
- For use on Telecom TNV-3 circuit, or 150V CAT IV power circuits
- Power blocking filter not required
- Environmental protection to IP54
- 2ns pulse for near end fault location
- AUTO option selecting gain and pulse for each range
- Display distance in metres or feet
- Uses five AA (LR6) primary cells
Four output impedances are available (25, 50, 75, and 100 Ω) and a velocity factor between 0.2 and 0.99 will meet any cable test requirements. An AUTO selection option ensures that the most effective parameters are selected depending on the range required, aiding rapid diagnosis of the TDR trace. A clear operator controlled cursor allows instant measurement of the distance to the fault. A trace HOLD feature also allows the operator to hold a trace on the screen, something not seen on most other handheld TDRs. Extra high resolution together with whitelight backlight and grey scale tones give the graphical display a vibrancy, aiding the user in identifying key events on the trace.
Features & Specification
Key Features | Large backlit display, Carry Case Included, IP54 Rated, Trace HOLD Feature, Simple Operation | ||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Product Stock Status | Next Day Delivery (subject to availability) | ||||||||||||||||||||||||||||||||||||||||
Manufacturer | Megger | ||||||||||||||||||||||||||||||||||||||||
Short Description |
DeliveryUpdated January 2024
Please note, our cut-off time is 2:00pmOrders requiring calibrationWhilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery. Bank/Public HolidaysPredicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scopeof our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order. *UK Mainland (Revised March 2021)
Delivery SurchargesBecause of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:
Offshore ServicesAll offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles. International deliveryInternational delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk ExportAll export inquiries should be directed to the export division before placement of order. If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
|