Fluke 6500-2 UK Portable Appliance Tester 4324475

£1,475.88

Specifications

Test Specifications The accuracy specification for the display range is defined as ±(%reading + digit counts) at 23 °C ±5 °C, ≤75 % RH.
Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C.
The measurement range meets the service operating errors specified in EN61557-1: 1997, EN61557-2: 1997, EN61557-4: 1997, EN61557-6: 1997, DIN VDE0404-2.
Power-on Test The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency.
Display Range 90 V to 264 V
Accuracy at 50 Hz ± (2% + 3 counts)
Resolution  0.1 V
Input Impedance       > 1 MΩ // 2.2 nF
Maximum Input Mains Voltage 264 V
Earth Bond Test (Rpe) Display Range 0 to 19.99 Ω
Accuracy (After Bond Test Zeroing) ± (2.5% + 4 counts)
Resolution 0.01 Ω
Test Current 200 mA AC -0% +40% into 1.99 Ω 
25 A AC ± 20% into 25 mΩ at 230 V
Open Circuit Voltage > 4 V AC, < 24 V AC
Bond Test Zeroing can subtract up to 1.99 Ω
Insulation Test (Riso) Display Range 0 to 299 MΩ
Accuracy ± (5% + 2 counts) from 0.1 to 300 MΩ
Resolution 0.01 MΩ (0 to 19.99 MΩ)
0.1 MΩ (20 to 199.9 MΩ)
1 MΩ (200 to 299 MΩ)
Test Voltage 500 V DC -0% + 25% at 500 kΩ load or 250 V dc -0 % +25 % at 250 kΩ load
Test Current > 1 mA at 500 kΩ load, < 15 mA at 0 Ω
Auto Discharge Time < 0.5 s for 1 μF
Max. Capacitive Load Operational up to 1 μF
Touch Current Test Display Range 0 to 1.99 mA AC
Accuracy ± (4% + 2 counts)
Resolution 0.01 mA
Internal Resistance (via Probe) 2 kΩ
Measuring Method Probe*
Substitute Leakage Current Test Display Range 0 to 19.99 mA AC
Accuracy ± (2.5% + 3 counts)
Resolution 0.01 mA
Test Voltage 100 V AC ± 20%
Load/Leakage Test: Load Current Display Range 0 A to 13 A
Accuracy ± (4% + 2 counts)
Resolution 0.1 A*
Load/Leakage Test: Load Power Display Range 230 V Mains 0.0 VA to 3.2 kVA
Accuracy  ± (5 % + 3 counts)
Resolution 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)*
Load/Leakage Test: Leakage Current Display Range 0 to 19.99 mA
Accuracy ± (4% + 4 counts)
Resolution 0.01 mA*
PELV Test Accuracy at 50 Hz ± (2% + 3 counts)
Overload Protection 300 V rms
Warning Threshold 25 V rms
RCD Test: Trip Current Operational Error ±10 %
Nominal 30 mA
Accuracy ±5 %
RCD Test: Trip Time Standard Requirement 61557 Part 6; tolerance of rated test current 0 % to +10 %
Operational Error ±10 %
RCD Type AC general-purpose 30 mA
Display Range 310 ms
Resolution 0.1 ms
Accuracy 3 ms
Trip Time Limit at 100 % (30 mA) 300 ms
Trip Time Limit at 500 % (150 mA) 40 ms
*The appliance under test is energized at mains potential.

 

Environmental Specifications

Operating Temperature 0 to 40 °C
Relative Humidity Non condensing < 10 °C
95% from 10 to 30 °C
75% from 30 to 40 °C

 

Safety Specifications

Safety Rating Complies with EN61010-1 3rd edition
CAT II, 300 V, pol 2

 

Mechanical & General Specifications

Size 200 mm (L) x 275 mm (W) x 114 mm (H)
Weight 3.13 kg
Power Supply 230 V +10 % -15 %, 50 Hz ±2 Hz or (6500-2 only: 110V +10 % -15 %,50 Hz ±2 Hz)
Power Consumption (Tester) 13 W typical (idle)
60 W max. during 25A Bond test
Storage Temperature -10 to 60 °C
Corrosion 70 °C @ 95 % RH for 5 days max.
Operating Altitude 0 up to 2000 m
Sealing IP-40 (enclosure), IP-20 (connectors)
EMC Complies with EN61326-1, portable
EMI Immunity 3 V/m

Description



isswww offer you a FREE quality accessory with purchases of selected PAT testers and PAT testing kits. Simply make your selection from the drop-down box above to add your order.


Fluke 6500-2 UK PAT Tester

low weight, small size, one-touch solution

The Fluke 6500-2 PAT tester is a low weight, small size, one-touch solution with redesigned auto-test capabilities to help you increase the number of portable appliance tests completed each day.  The 6500-2 is designed to enable you to work faster without compromising test results.

One-Touch Solution…

Pre-set test routines are initiated from a single button. This not only simplifies testing but also facilitates a faster, more efficient way of working. The fully automatic 6500-2 also includes user-definable test routines and a QWERTY keyboard for rapid data entry.

Low Weight…

Weighing approximately 3 kg, the 6500-2 is lightweight and easy to carry when working on-site. The hard rugged carrying case (supplied) not only offers protection during transit but also includes extra storage space for accessories and other tools.

Small Size…

This portable appliance testers is also extremely compact, and has Fluke’s traditional ruggedness to be able to withstand working in the field. Packed with all the features you need for testing portable appliances, a Fluke PAT tester is a complete all-in-one solution.

Fluke 6500-2 UK Includes: 

  • Fluke 6500-2 Portable Appliance Tester
  • Appliance Pass Labels
  • EXTL100 Extension Lead Test Adapter
  • Fluke DMS/0702 Portable Appliance Tester Software
  • User's manual on CD
  • Quick reference guide
  • Hard carrying case
  • Test lead
  • Test probe
  • Crocodile clip
  • Mains cord
  • USB stick
  • USB cable

Fluke Simplifies Portable Appliance Testing

  • Dedicated key for each test for ‘one-touch’ testing
  • Pre-set pass/fail levels to save time
  • Large backlit display for easy reading
  • Single mains socket for appliance connection
  • Separate IEC socket for easy mains/extension lead testing
  • Detachable test leads for quick field replacement
  • Integral carrying handle
  • USB port for data transfer
  • Integral QWERTY keyboard for rapid data entry
  • Additional USB memory capability for back-up data storage and transfer to PC
  • Large backlit graphics display
  • Pre-set, auto-test sequences for user convenience
  • Integral site, location and description codes for faster data processing
  • Memory review facility for more on-site control
  • USB port for data transfer

isswww and Fluke Instruments 

Fluke Corporation is the world leader in the manufacture, distribution and service of electronic test tools and software.  

Since its founding in 1948, Fluke has helped define and grow a unique technology market, providing testing and troubleshooting capabilities that have grown to status in manufacturing and service industries. Every new manufacturing plant, office, hospital, or facility built today represents another potential customer for Fluke products.  

From industrial electronic installation, maintenance and service, to precision measurement and quality control, Fluke tools help keep business and industry around the globe up and running. Typical customers and users include technicians, engineers, meteorologists, medical-device manufacturers, and computer network professionals, people who stake their reputations on their tools, and use tools to help extend their personal power and abilities.  

Fluke are a founding core supplier of ISSWWW and we enjoy a personal and professional relationship with them. We have Fluke trained staff on site and we hold an extensive range of their products. Our customers know that when it comes to Fluke products, we have great prices and exceptional advice and support services, reassuring when you need to make that all-important purchase. 

Features & Specification

More Information
Key Features Memory function, Downloadable, Colour display, Test 110v appliances, QWERTY Keyboard, Fast report generation
Product Stock Status Next Day Delivery (subject to availability)
Manufacturer Fluke Testers
Short Description

Specifications

Test Specifications The accuracy specification for the display range is defined as ±(%reading + digit counts) at 23 °C ±5 °C, ≤75 % RH.
Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C.
The measurement range meets the service operating errors specified in EN61557-1: 1997, EN61557-2: 1997, EN61557-4: 1997, EN61557-6: 1997, DIN VDE0404-2.
Power-on Test The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency.
Display Range 90 V to 264 V
Accuracy at 50 Hz ± (2% + 3 counts)
Resolution  0.1 V
Input Impedance       > 1 MΩ // 2.2 nF
Maximum Input Mains Voltage 264 V
Earth Bond Test (Rpe) Display Range 0 to 19.99 Ω
Accuracy (After Bond Test Zeroing) ± (2.5% + 4 counts)
Resolution 0.01 Ω
Test Current 200 mA AC -0% +40% into 1.99 Ω 
25 A AC ± 20% into 25 mΩ at 230 V
Open Circuit Voltage > 4 V AC, < 24 V AC
Bond Test Zeroing can subtract up to 1.99 Ω
Insulation Test (Riso) Display Range 0 to 299 MΩ
Accuracy ± (5% + 2 counts) from 0.1 to 300 MΩ
Resolution 0.01 MΩ (0 to 19.99 MΩ)
0.1 MΩ (20 to 199.9 MΩ)
1 MΩ (200 to 299 MΩ)
Test Voltage 500 V DC -0% + 25% at 500 kΩ load or 250 V dc -0 % +25 % at 250 kΩ load
Test Current > 1 mA at 500 kΩ load, < 15 mA at 0 Ω
Auto Discharge Time < 0.5 s for 1 μF
Max. Capacitive Load Operational up to 1 μF
Touch Current Test Display Range 0 to 1.99 mA AC
Accuracy ± (4% + 2 counts)
Resolution 0.01 mA
Internal Resistance (via Probe) 2 kΩ
Measuring Method Probe*
Substitute Leakage Current Test Display Range 0 to 19.99 mA AC
Accuracy ± (2.5% + 3 counts)
Resolution 0.01 mA
Test Voltage 100 V AC ± 20%
Load/Leakage Test: Load Current Display Range 0 A to 13 A
Accuracy ± (4% + 2 counts)
Resolution 0.1 A*
Load/Leakage Test: Load Power Display Range 230 V Mains 0.0 VA to 3.2 kVA
Accuracy  ± (5 % + 3 counts)
Resolution 1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)*
Load/Leakage Test: Leakage Current Display Range 0 to 19.99 mA
Accuracy ± (4% + 4 counts)
Resolution 0.01 mA*
PELV Test Accuracy at 50 Hz ± (2% + 3 counts)
Overload Protection 300 V rms
Warning Threshold 25 V rms
RCD Test: Trip Current Operational Error ±10 %
Nominal 30 mA
Accuracy ±5 %
RCD Test: Trip Time Standard Requirement 61557 Part 6; tolerance of rated test current 0 % to +10 %
Operational Error ±10 %
RCD Type AC general-purpose 30 mA
Display Range 310 ms
Resolution 0.1 ms
Accuracy 3 ms
Trip Time Limit at 100 % (30 mA) 300 ms
Trip Time Limit at 500 % (150 mA) 40 ms
*The appliance under test is energized at mains potential.

 

Environmental Specifications

Operating Temperature 0 to 40 °C
Relative Humidity Non condensing < 10 °C
95% from 10 to 30 °C
75% from 30 to 40 °C

 

Safety Specifications

Safety Rating Complies with EN61010-1 3rd edition
CAT II, 300 V, pol 2

 

Mechanical & General Specifications

Size 200 mm (L) x 275 mm (W) x 114 mm (H)
Weight 3.13 kg
Power Supply 230 V +10 % -15 %, 50 Hz ±2 Hz or (6500-2 only: 110V +10 % -15 %,50 Hz ±2 Hz)
Power Consumption (Tester) 13 W typical (idle)
60 W max. during 25A Bond test
Storage Temperature -10 to 60 °C
Corrosion 70 °C @ 95 % RH for 5 days max.
Operating Altitude 0 up to 2000 m
Sealing IP-40 (enclosure), IP-20 (connectors)
EMC Complies with EN61326-1, portable
EMI Immunity 3 V/m

Delivery

Updated January 2024

Please note, our cut-off time is 2:00pm

Orders requiring calibration 

Whilst we take the greatest care to get all orders dispatched and delivered to you in the stated time frame, orders received PM and requiring calibration may on occasion miss dispatch that day, according to the complexity of the calibration.
Be assured they will ship on the next dispatch this in most cases should not add more than 24 hours to your delivery.

Bank/Public Holidays

Predicted delivery times are based on regular trading days Monday to Friday. Public holidays, bank holidays and weekends are outside the usual scope
of our dispatch and subject to activities/holidays of our carriers and therefore may incur additional days lead time to your order.

*UK Mainland (Revised March 2021)

Service Price
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value OVER £75.00 ex VAT FREE
Standard FREE 2-3 Day Courier Delivery – UK Mainland only - Zones A & B - Order value UNDER £75.00 ex VAT £4.95
Next WORKING Day (excludes Saturdays, Sundays and public holidays)  – UK Mainland only - Zones A & B  - ANY order value - Order by 2:00pm £7.75
Saturday ANYTIME Delivery - Order by 2:00pm £9.95
 

 

 

 

 

Delivery Surcharges

Because of the high cost of carriage, we regretfully need to apply a surcharge on all deliveries made in the following regions:

  • Zones A & B  - Mainland delivery rates apply. 
  • Zone C - Scottish Highlands (Charges are calculated at the checkout).
  • Zone D - Outer Hebrides, Orkney Isles, Shetland Isles, Isle of Man, Scilly Isles, and Channel Islands (Charges are calculated at the checkout).
  • Zone E - Northern Ireland (Charges are calculated at the checkout).
  • Zone F - Republic of Ireland (Charges are calculated at the checkout).

Offshore Services

All offshore deliveries are a 3-4 day service as standard. This includes Channel Islands, Northern & Southern Ireland, Scottish Islands, Isle of Man and the Scilly Isles.

International delivery

International delivery charges are automatically added to your order at the checkout. For any questions regarding international deliveries please contact us at sales@isswww.co.uk

Export 

All export inquiries should be directed to the export division before placement of order.

If no shipping option is available to your selected country please call us FREE on 0800 0224 060 to discuss your requirements.
All stated prices are subject to VAT at the current rate where applicable.
E&OA